ABC Aluminum Aerial Bundle Cables IEC 60502-1

ABC (Aerial Bundled Cable) is primarily used for overhead power distribution applications such as street lighting, outdoor lighting, rural electrification, and temporary power supply at construction sites.

  • Abc Aluminum Aerial Bundle Cables Iec 60502 1

ABC Aluminum Aerial Bundle Cables IEC 60502-1


ABC Aluminum Aerial Bundle Cables IEC 60502-1

  • Voltage 0.6/1kV
  • Conductor Aluminium conductor
  • Insulation PE /XLPE/PVC
  • Number of cores 2-5 cores
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

Application

ABC (Aerial Bundled Cable) is primarily used for overhead power distribution applications such as street lighting, outdoor lighting, rural electrification, and temporary power supply at construction sites.
These cables are designed for systems with voltages up to 1000V phase-to-phase.

  • Operating Temperature:

    • Up to 70°C for PE or PVC insulated conductors

    • Up to 90°C for XLPE insulated conductors

  • Installation: Suitable for outdoor overhead use. The black insulation is UV and weather resistant.


Standards

  • GB/T 12527 (Equivalent to IEC 60502-1): Aerial Insulated Cables for Rated Voltages up to and Including 1kV

  • IEC 60228: Conductors of Insulated Cables


Construction

ComponentDescription
ConductorStranded circular aluminum (AAC), aluminum alloy (AAAC), copper (Cu), or ACSR. Available in compacted or uncompacted forms.
InsulationPE, PVC, or XLPE – black, UV and weather resistant.

Cable Types and Sizes

TypeNumber of CoresNominal Cross Section (mm²)
CU/PVC, AAC/PVC, AAAC/PVC110 ~ 400
CU/PE, AAC/PE, AAAC/PE110 ~ 400
CU/XLPE, AAC/XLPE, AAAC/XLPE110 ~ 400
AAC/PVC, AAC/PE, AAC/XLPE2, 410 ~ 120
AAC/PVC, AAC/PE, AAC/XLPE3 + k*10 ~ 120

*The auxiliary core 'k' is typically used as a load-bearing or neutral conductor. Its cross-sectional area is selected based on project or customer requirements.

  • (A) = Steel wire messenger

  • (B) = Aluminum alloy messenger


Features

  • Lightweight and easy to install

  • Improved safety compared to bare conductors

  • Resistant to UV, moisture, and mechanical damage

  • Suitable for high-humidity or salt-laden environments


Contact Us

Looking for a reliable supplier of ABC aerial bundled cables compliant with IEC 60502-1?
TOT Wire & Cable provides high-quality, competitively priced overhead bundled cables suitable for power distribution projects.

PARAMETER - GB/T 12527 :
(Equ. IEC 60502-1)

Nominal SizeMin. No. of WiresApprox.
Diameter of Conductor
Nominal
Thickness of Insulation
Max. Diameter of CableMax. DC Resistance
at 20 0C
Breaking Load
Hard copperAnnealedcopperHard copper
mm²No.mmmmmmΩ/kmΩ/kmN
1063.81.06.51.9061.833471
1664.81.28.01.1981.155486
2566.01.29.40.7490.7278465
3567.01.411.00.5400.52411731
5068.41.412.30.3990.38716052
701210.01.414.10.2760.26823461
951511.61.616.50.1990.19331759
1201813.01.618.10.1580.15339911
1501814.61.820.20.1280.12449505
1853016.22.022.50.10210.099161846
2403418.42.225.60.07770.075479823
Nominal SizeMin. No. of WiresApprox.
Diameter of Conductor
Nominal
Thickness of Insulation
Max. Diameter of CableMax. DC Resistance
at 20 0C
Breaking Load
AACAAACAACAAAC
mm²No.mmmmmmΩ/kmΩ/kmNN
1063.81.06.53.083.57416502514
1664.81.28.01.912.21725174022
2566.01.29.41.201.39337626284
3567.01.411.00.8681.00751778800
5068.41.412.30.6410.744701112569
701210.01.414.10.4430.5141035417596
951511.61.616.50.3200.3711372723880
1201513.01.618.10.2530.2941733930164
1501514.61.820.20.2060.2392103337706
1853016.22.022.50.1640.1902673246503
2403018.42.225.60.1250.1453467960329
3003020.82.227.20.1000.1164334975411
4005323.22.230.70.07780.090455707100548
PARAMETER - BS 6485,BS7884 :

PVC-Covered Conductors For Overhead Power Lines

Nominal cross-sectional areaStranding and Wire DiameterApproximate Overall Diameter of Bare ConductorMaximum Resistance per kilometre at 20 °CApproximate Breaking LoadApproximate Overall Diameter of Covered ConductorApproximate Mass per kilometre of Covered Conductor
Type 8Type 16Type 8Type 16
mm²mmmmΩkNmmmmkgkg
CU/PVC
147/1.604.801.3035.7446.88.4160190
163/2.655.701.1066.5907.79.3180220
323/3.758.060.552012.7110.512.1350390
357/2.507.500.533714.0979.911.5360400
707/3.5510.650.264626.8813.514.7690750
1007/4.3012.900.181037.6415.716.99901060

PVC-Covered Conductors For Overhead Power Lines

Nominal cross-sectional areaStranding and Wire DiameterApproximate Overall Diameter of Bare ConductorMaximum Resistance per kilometre at 20 °CApproximate Breaking LoadApproximate Overall Diameter of Covered ConductorApproximate Mass per kilometre of Covered Conductor
Type 16Type 16
mm²mmmmΩkNmmkg
COPPER-ALLOY / PVC
123/2.304.951.7807.208.2170
227/2.006.001.01112.949.6270
387/2.607.800.598321.6911.8430
757/3.7011.100.295440.2315.1810
12519/2.9014.500.178468.7518.51310
15019/3.2016.000.146582.1620.01570

Aerial Insulated Cables for Rated Voltages Up To And Including 1kV AAC/XLPE

Number of Cores and SizeMin. No. of WiresNominal Insulation ThicknessApprox.  Diameter of CableMax. DC. Resistance at 20℃Breaking LoadApprox .
weight
mm²No.mmmmΩ/kmkNkg/km
1x1061.05.83.081.65041
1x1661.27.21.912.51765
1x2561.28.41.203.76294
1x3561.49.80.8685.177129
1x5061.410.90.6417.011166
1x70121.412.60.44310.354229
1x95151.614.80.32013.727315
1x120151.616.00.25317.339386
1x150151.818.10.20621.033476
1x185302.020.10.16426.732594
1x240302.222.80.12534.679777
1x300302.224.90.10043.349955
1x400532.227.60.077855.7071205
2x1061.011.63.081.65084
2x1661.214.41.912.517131
2x2561.216.81.203.762189
2x3561.419.60.8685.177261
2x5061.421.80.6417.011336
2x70121.425.20.44310.354463
2x95151.629.60.32013.727637
2x120151.632.00.25317.339779
4x1061.014.03.081.650167
4x1661.217.41.912.517262
4x2561.220.31.203.762378
4x3561.423.70.8685.177522
4x5061.426.40.6417.011672
4x70121.430.50.44310.354926
4x95151.635.80.32013.7271274
4x120151.638.70.25317.3391558
PARAMETER - BS 6485,BS 3242

 PVC-Covered Conductors For Overhead Power Lines

Nominal cross-sectional areaStranding and Wire DiameterApproximate Overall Diameter of Bare ConductorMaximum Resistance per kilometre at 20 °CApproximate Breaking LoadApproximate Overall Diameter of Covered ConductorApproximate Mass per kilometre of Covered Conductor
Type 16Type 16
mm²mmmmΩkNmmkg
AAAC / PVC
257/2.347.021.0948.4410.6170
507/3.309.900.549816.8013.9280
1007/4.6513.950.276933.3018.0470
15019/3.4817.400.183050.6521.4680
20019/3.7618.800.156859.1022.8780