AL XLPE Multiplexed Cable 0.6/1kV – Bare Neutral

The AL XLPE Multiplexed Cable 0.6/1kV with Bare Neutral is a specialized low-voltage power cable designed for indoor and outdoor electrical distribution applications. It features cross-linked polyethylene (XLPE) insulation and multiple conductors, including a bare neutral conductor, suitable for various power and control circuits.

  • slide

AL XLPE Multiplexed Cable 0.6/1kV - Bare Neutral


  • Cable Type Multiplexed Cable
  • Number of cores Duplex, Triplex, Quadruplex
  • Conductor Aluminum
  • Insulation XLPE
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

AL XLPE Multiplexed Cable 0.6/1kV - Bare Neutral Application

Power distribution in industrial, commercial, and residential buildings
Indoor wiring for switchboards, motor connections, and control panels
Outdoor applications where flexible, durable, and reliable cabling is required
Systems requiring multiplexed conductors with a shared sheath for ease of installation

AL XLPE Multiplexed Cable 0.6/1kV - Bare Neutral Standard

ABNT NBR 8182 - Self-sustained multiplex power cables with extruded insulation of PE or XLPE, for voltages up to 0,6/1 kV - Performance requirements.
ABNT NBR NM 280 - Conductors of insulated cables (IEC 60228, MOD).
ABNT NBR 10298 - Bare cables with alloy aluminum-magnesium-silicon, for overhead lines

CONSTRUCTION :

Phase Conductor:
Bare 1350 aluminum wires, soft temper. Class 2 stringing.

Insulation:
XLPE 90°C. Thermosetting compound of cross-linked polyethylene with at least 2% carbon black.

Neutral Conductor:
Bare 1350 aluminum wires, H19 temper (AC Neutral).

Driver Identification:
Duplex: PT + No
Triplex: FR/CZ + Nu
Quadruplex: PT/CZ/VM + Nu

TECHNICAL DATA

Maximum conductor temperature Permanently: 90°C
Overload: 130°C
Short circuit: 250°C

Parameter

Type Nominal Section (mm²) Phase Conductor Neutral Conductor Approx outer diameter (mm) Liquid Weight (kg/km)
Conductor Diameter (mm) Insulation Thickness (mm) Maximum Electrical Resistance (Ω/km) Formation (number of wires x mm) Min Rupture Load (kgf)
THAT CAL
Duplex 1x10 + 10 4,0 1,2 3,08 7x1,36 199 - 10,5 74
1x16 + 16 4,7 1,2 1,91 7x1,70 306 - 12,2 109
1x25 + 25 5,9 1,4 1,20 7x2,11 455 - 15,0 167
1x35 + 35 6,9 1,6 0,87 7x2,50 626 1113 17,6 231
1x50 + 50 8,1 1,6 0,64 7x3,00 852 1602 20,3 311
Triplex 2x10 + 10 4,0 1,2 3,08 7x1,36 199 - 13,8 119
2x16 + 16 4,7 1,2 1,91 7x1,70 306 - 15,3 173
2x25+25 5,9 1,4 1,20 7x2,11 455 - 18,8 266
2x35+35 6,9 1,6 0,87 7x2,50 626 1113 21,8 367
2x50+50 8,1 1,6 0,64 7x3,00 852 1602 24,4 485
Quadruplex 3x10 + 10 4,0 1,2 3,08 7x1,36 199 - 15,4 165
3x16 + 16 4,7 1,2 1,91 7x1,70 306 - 17,0 238
3x25+25 5,9 1,4 1,20 7x2,11 455 - 20,9 365
3x35 + 35 6,9 1,6 0,87 7x2,50 626 1113 24,2 502
3x50 + 50 8,1 1,6 0,64 7x3,00 852 1602 27,1 660
3x70 + 70 9,7 1,8 0,44 7x3,45 1102 2030 31,9 920
3x95+70 11,5 2,0 0,32 7x3,45 1102 2030 37,2 1185
3x120 + 70 12,9 2,0 0,25 7x3,45 1102 2030 40,6 1415
The values ​​are nominal and subject to variations provided for in the standard.