AL XLPE Multiplexed Cable 0.6/1kV – Insulated Neutral

The AL XLPE Multiplexed Cable 0.6/1kV with Insulated Neutral is a low-voltage power cable designed for efficient and safe electrical distribution in various industrial, commercial, and residential applications. It features cross-linked polyethylene (XLPE) insulation for the phase conductors and an insulated neutral conductor, providing enhanced safety and performance.

  • slide

AL XLPE Multiplexed Cable 0.6/1kV - Insulated Neutral


  • Cable Type Multiplexed Cable
  • Number of cores Duplex, Triplex, Quadruplex
  • Conductor Aluminum
  • Insulation XLPE
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

AL XLPE Multiplexed Cable 0.6/1kV - Insulated Neutral Application

Power supply wiring for industrial machinery, control panels, and switchgear
Indoor and outdoor electrical distribution systems
Underground or concealed wiring where additional insulation is required
Systems that demand a high level of safety and reliability with insulated neutral conductors

AL XLPE Multiplexed Cable 0.6/1kV - Insulated Neutral Standard

ABNT NBR 8182 - Self-sustained multiplex power cables with extruded insulation of PE or XLPE, for voltages up to 0,6/1 kV - Performance requirements.
ABNT NBR NM 280 - Conductors of insulated cables (IEC 60228, MOD).
ABNT NBR 10298 - Bare cables with alloy aluminum-magnesium-silicon, for overhead lines

CONSTRUCTION :

Phase Conductor:
Bare 1350 aluminum wires, soft temper. Class 2 stringing.

Insulation:
XLPE 90°C. Thermosetting compound of cross-linked polyethylene with at least 2% carbon black.

Neutral Conductor:
Bare 1350 aluminum wires, H19 temper (AC Neutral).

Driver Identification:
Duplex: PT + No
Triplex: FR/CZ + Nu
Quadruplex: PT/CZ/VM + Nu

TECHNICAL DATA

Maximum conductor temperature Permanently: 90°C
Overload: 130°C
Short circuit: 250°C

Parameter

Type Nominal Section (mm²) Phase Conductor Neutral Conductor Approx outer diameter (mm) Net Weight (kg/km)
Conductor Diameter (mm) Insulation Thickness (mm) Maximum Electrical Resistance (Ω/km) Formation (number of wires x mm) Insulation Thickness (mm) Min Breaking Load (kgf)
HERE LIME
Duplex 1x10 + 10 4.0 1.2 3.08 7x1.36 1.2 199 - 12.9 96.4
1x16 + 16 4.7 1.2 1.91 7x1.70 1.2 306 - 14.6 135
1x25 + 25 5.9 1.4 1.20 7x2.11 1.4 455 - 17.8 207
1x35 + 35 6.9 1.6 0.87 7x2.50 1.6 626 1113 20.8 284
1x50 + 50 8.1 1.6 0.64 7x3.00 1.6 852 1602 23.5 377
Triplex 2x10 + 10 4.0 1.2 3.08 7x1.36 1.2 199 - 13.8 142
2x16 + 16 4.7 1.2 1.91 7x1.70 1.2 306 - 15.6 199
2x25 + 25 5.9 1.4 1.20 7x2.11 1.4 455 - 19.2 304
2x35 + 35 6.9 1.6 0.87 7x2.50 1.6 626 1113 22.4 420
2x50 + 50 8.1 1.6 0.64 7x3.00 1.6 852 1602 25.3 551
Quadruplex 3x10 + 10 4.0 1.2 3.08 7x1.36 1.2 199 - 15.4 188
3x16 + 16 4.7 1.2 1.91 7x1.70 1.2 306 - 17.3 264
3x25 + 25 5.9 1.4 1.20 7x2.11 1.4 455 - 21.3 403
3x35 + 35 6.9 1.6 0.87 7x2.50 1.6 626 1113 24.8 555
3x50 + 50 8.1 1.6 0.64 7x3.00 1.6 852 1602 28.0 726
3x70 + 70 9.7 1.8 0.44 7x3.45 1.8 1102 2030 32.6 1004
3x95 + 70 11.5 2.0 0.32 7x3.45 2.0 1102 2030 37.9 1270
3x120 + 70 12.9 2.0 0.25 7x3.45 2.0 1102 2030 41.3 1500
The values ​​are nominal and subject to variations provided for in the standard.