Screened MV ABC Cable Application:
Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.Primarily used for overhead service applications such as street lighting,outdoor lighting,and temporary service for construction. To be used at votages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75℃ for polyethylence insulated conductors or 90℃ for crossliked polyethylene(XLPE) insulated conductors
Screened MV ABC Cable Strandard
IEC 60502
Screened MV ABC Cable Construction
Phase Conductor | Circular Compacted Stranded H68 Aluminium ( Class 2) |
Conductor Screen | Extruded Semi-conductive Layer. |
Insulation | XLPE. |
Insulation Screen | Extruded Semi-conductive Layer. |
Metallic Screen | Copper wire screen or copper tape screen |
Separator | Semi-conductive swellable tape. |
Outer Sheath | HDPE. |
Support Conductor | Galvanized steel wires. |
Assembly | XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay |

Screened MV ABC Cable Construction
Screened MV ABC Cable Technical Data
Temperature :
- Normal operation 90°C.
- Emergency over load conditions 130°C.
- Short circuit conditions 250°C.
6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to IEC 60502 Parameter
NO.Cores X Nominal Cross Section |
Phase Conductor | Messenger Suspension Unit | Contiuous Current Rating at 300C Ambient Temp |
|||
Stranding | Nominal Sectional Area | Stranding | Nominal Sectional Area | Breaking Load | ||
No.×mm² | No.×mm | mm2 | No.×mm | mm2 | KN | A |
3X50 + 1X25 | 19/1.78 | 50 | 7/3.0 | 50 | 60 | 116 |
3X70 + 1X50 | 19/2.14 | 70 | 7/3.15 | 50 | 62 | 210 |
3X95+ 1X50 | 19/2.52 | 95 | 7/3.0 | 50 | 60 | 173 |
3X185+1X120 | 37/2.52 | 185 | 7/4.67 | 120 | 150 | 259 |
3X150 +1X50 | 37/2.25 | 150 | 7/3.15 | 50 | 62 | 365 |
3X240 +1X50 | 61/2.25 | 240 | 7/3.15 | 50 | 62 | 500 |