3-Layer 15kV AAAC Tree Wire Spacer Cable

The 3-Layer 15kV AAAC Tree Wire Spacer Cable is designed for overhead electrical distribution lines requiring high mechanical strength, excellent electrical performance, and reliable conductor separation. Its three-layer layered configuration with spacers ensures optimal conductor spacing, line stability, and durability, making it suitable for urban, suburban, and environmentally sensitive installations.

  • slide

3-Layer 15kV AAAC Tree Wire Spacer Cable


3-Layer 15kV AAAC Tree Wire Spacer Cable

  • Conductor 6201-81 aluminum alloy (AAAC)
  • Insulation Cross-linked polyethylene(XLPE)
  • Sheath High-density track-resistant Polyethylene(HDPE)
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

3-Layer 15kV AAAC Tree Wire Spacer Cable Application

The tree wire is used for primary and secondary overhead distribution where limited space is available or desired for rights-of-way. Installed the same as bare conductors, however, covering is effective in preventing direct shorts and instantaneous flashovers with other objects. The close-proximity configuration minimizes the amount of space and hardware required for line installation, making it particularly useful in congested areas such as alleyways or tight corridors.

3-Layer 15kV AAAC Tree Wire Spacer Cable Standard

ICEA S-121-733, ASTM B231, ASTM B399, ASTM B232

Construction

3-Layer 15kV AAAC Tree Wire Spacer Cable Construction
The tree wire is designed with concentrically stranded conductors - AAC (1350-H19) which are either compressed or compact depending on conductor size, available with AAAC or ACSR. The conductors can be covered with high-density track-resistant Polyethylene (HDTRPE) or track-resistant crosslinked Polyethylene (XLPE) insulation to meet different applications.

TECHNICAL DATA :

Temperature :

- Normal operation 90°C.

- Emergency over load conditions 130°C.

- Short circuit conditions 250°C.

Voltage rating :

15 kV phase to phase AC TESTING VOLTAGE : 27 kV for 5 minutes

3-Layer 15kV AAAC Tree Wire
Size
(kcmil)
Equivalent
AAC (AWG or kcmil)
Stranding Conductor Covering Thickness (mils) Cable O.D. Rated Weight per
Diameter Strength 1000 ft.
(mils) Conductor Shield Inner Layer Outer Layer (mils) (lbs) (lbs)
48.69 4 7 250 15 75 75 580 1584 137
77.47 2 7 316 15 75 75 646 2520 179
123.3 1/0 7 398 15 75 75 728 4014 241
155.4 2/0 7 447 15 75 75 777 4851 283
195.7 3/0 7 502 15 75 75 832 6111 334
246.9 4/0 7 563 15 75 75 893 7704 397
312.8 266.8 19 642 15 75 75 972 9900 473
394.5 336.4 19 720 15 75 75 1050 11970 568
465.4 397.5 19 783 15 75 75 1113 14040 649
559.5 477 19 858 15 75 75 1188 16920 755
652.4 556.5 19 927 20 75 75 1267 19710 894