ICEA S-121-733 Tree Wire Spacer Cable

This cable is designed for overhead power distribution systems, specifically as "tree wire" or "spacer cable." It's a type of covered conductor, not a fully insulated cable, so its performance depends on the entire system, including insulators and spacers. It does not carry a voltage rating on its own.

  • Icea S 121 733 Tree Wire Spacer Cable

ICEA S-121-733 Tree Wire Spacer Cable


SAC Cable ICEA S-66-524

  • Conductor Compact stranded hard drawn aluminum conductor (Class 2)
  • Conductor shield Semi-conducting cross-linked polyethylene.
  • Insulation High-density cross-linked polyethylene (XLPE)
  • Covering Abrasion-resistant, track-resistant cross-linked polyethylene (Black)
  • Configuration Designed for use with spacers on overhead distribution systems
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

This cable is designed for overhead power distribution systems, specifically as 'tree wire' or 'spacer cable.' It's a type of covered conductor, not a fully insulated cable, so its performance depends on the entire system, including insulators and spacers. It does not carry a voltage rating on its own.


Construction and Materials

The core conductor is a compact stranded hard-drawn aluminum (Class 2), though other materials like ACSR and copper are also possible. A semi-conducting cross-linked polyethylene layer acts as a conductor shield. The primary insulation is high-density cross-linked polyethylene (XLPE). An outer layer of abrasion-resistant, track-resistant XLPE provides extra protection against physical damage and electrical tracking. The cable is designed to be used with spacers on overhead distribution systems.


Standards and Ratings

The cable adheres to several standards, including:

  • ANSI/ICEA S-121-733 for Tree Wire and Messenger Supported Spacer Cable.
  • NTC 5909 (Colombia's standard for covered power cables).
  • BS EN 50397-1 (a European standard for covered conductors).

The cable's construction supports normal service temperatures of C for thermoplastic polyethylene (PE) and C for cross-linked polyethylene (XLPE).

15kV Tree Wire
Size
(AWG or kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 15kV ACSR/XLPE/HDPE
66/10.381.911.9113.65.28188
46/10.381.911.9114.88.30238
36/10.381.911.9115.610.2271
26/10.381.911.9116.512.7313
16/10.381.911.9117.415.6362
1/06/10.381.911.9118.519.4424
2/06/10.381.911.9119.623.3496
3/06/10.381.911.9120.729.4584
4/06/10.381.911.9122.437.1699
266.818/10.381.911.9123.730.3713
336.418/10.381.911.9125.238.2847

 

Size
( kcmil)
Number
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 15kV AAAC/XLPE/HDPE
48.6970.381.911.9115.27.83223
77.4770.381.911.9116.812.4286
123.370.381.911.9119.018.9383
155.470.381.911.9120.123.8443
195.770.381.911.9121.530.0521
246.970.381.911.9123.037.8614
312.8190.381.911.9124.946.5740
394.5190.381.911.9127.458.6892
465.4190.381.911.9128.469.21008
559.5190.511.911.9130.483.11168
652.4190.511.911.9131.897.01320
740.8370.511.911.9133.31071463

 

Size
(AWG or kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 15kV AAC/XLPE/HDPE
470.381.911.9114.43.52204
270.381.911.9115.85.39259
1/070.381.911.9117.77.96341
2/070.381.911.9118.69.99394
3/070.381.911.9119.712.15459
4/070.381.911.9121.115.30541
266.8190.381.911.9123.019.89648
336.4190.381.911.9124.924.57775
397.5190.381.911.9126.128.44878
477190.381.911.9127.933.301017
556.5370.511.911.9130.139.871161
636370.511.911.9131.545.361295
795370.512.032.0334.255.621557
25kV Tree Wire
Size
(AWG or kcmil)
No.
of Wires
Covering ThicknessCable diameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 25kV ACSR/XLPE/HDPE
1/06/10.383.183.1823.619.4586
2/06/10.383.183.1824.723.3666
3/06/10.383.183.1825.829.4763
4/06/10.383.183.1827.537.1891
266.818/10.383.183.1828.630.3913
336.418/10.383.183.1830.138.21058

 

Size
( kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 25kV AAAC/XLPE/HDPE
48.6970.383.183.1820.17.83358
77.4770.383.183.1821.712.4434
123.370.383.183.1823.918.9547
155.470.383.183.1825.023.8616
195.770.383.183.1826.430.0704
246.970.383.183.1827.937.8809
312.8190.383.183.1829.646.5939
394.5190.383.183.1832.158.61109
465.4190.383.183.1833.169.21232
559.5190.513.183.1835.183.11407
652.4190.513.183.1836.597.01569
740.8370.513.183.1838.01071723
927.2370.513.183.1840.91352050

 

Size
(AWG or kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 25kV AAC/XLPE/HDPE
1/070.383.183.1822.87.96497
2/070.383.183.1823.79.99556
3/070.383.183.1824.812.15630
4/070.383.183.1826.215.30723
266.8190.383.183.1827.719.89833
336.4190.383.183.1829.624.57973
397.5190.383.183.1830.828.441086
477190.383.183.1832.633.301237
556.5370.513.183.1834.839.871398
636370.513.183.1836.245.361542
795370.513.183.1838.955.621824
35kV Tree Wire
Size
(AWG or kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 35kV ACSR/XLPE/HDPE
1/06/10.384.453.1826.119.4682
2/06/10.384.453.1827.223.3767
3/06/10.384.453.1828.429.4868
4/06/10.384.453.1830.037.11002
266.818/10.384.453.1831.130.31028
336.418/10.384.453.1832.638.21179
Size
( kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 35kV AAAC/XLPE/HDPE
48.6970.384.453.1822.67.83441
77.4770.384.453.1824.212.4523
123.370.384.453.1826.418.9644
155.470.384.453.1827.523.8718
195.770.384.453.1828.930.0811
246.970.384.453.1830.437.8922
312.8190.384.453.1832.146.51059
394.5190.384.453.1834.658.61238
465.4190.384.453.1835.669.21365
559.5190.514.453.1837.683.11547
652.4190.514.453.1839.097.01715
740.8370.514.453.1840.51071874
927.2370.514.453.1843.41352213
Size
(AWG or kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 35kV AAC/XLPE/HDPE
1/070.384.453.1825.37.96590
2/070.384.453.1826.29.99653
3/070.384.453.1827.312.15731
4/070.384.453.1828.715.30829
266.8190.384.453.1830.219.89946
336.4190.384.453.1832.124.571094
397.5190.384.453.1833.328.441210
477190.384.453.1835.133.301369
556.5370.514.453.1837.339.871538
636370.514.453.1838.845.361688
795370.514.453.1841.455.621980
46kV Tree Wire
Size
(kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 46kV AAAC/XLPE/HDPE
48.6970.385.724.4527.77.83640
77.4770.385.724.4529.312.4734
123.370.385.724.4531.518.9873
155.470.385.724.4532.623.8955
195.770.385.724.4534.030.01060
246.970.385.724.4535.537.81182
312.8190.385.724.4537.246.51332
394.5190.385.724.4539.758.61531
465.4190.385.724.4540.769.21666
559.5190.515.724.4542.783.11864
652.4190.515.724.4544.197.02043
740.8370.515.724.4545.61072214
927.2370.515.724.4548.51352575

 

Size
(AWG or kcmil)
No.
of Wires
Covering ThicknessCable DiameterRated
Strength
Weight
Conductor ShieldInner LayerOuter Layer
No.mmmmmmmmkNkg/km
3-Layer 46kV AAC/XLPE/HDPE
1/070.385.724.4530.47.96810
2/070.385.724.4531.39.99880
3/070.385.724.4532.412.15968
4/070.385.724.4533.815.301077
266.8190.385.724.4535.319.891205
336.4190.385.724.4537.224.571367
397.5190.385.724.4538.428.441494
477190.385.724.4540.233.301666
556.5370.515.724.4542.439.871853
636370.515.724.4543.945.362014
795370.515.724.4546.555.622326
Need Help?