AAAC-All Aluminum Alloy Conductors ASTM B 399

Our AAAC (All Aluminum Alloy Conductors) are engineered in accordance with IEC 61089 standards, offering an optimal balance of strength, lightweight design, and excellent electrical performance. Made from high-quality aluminum alloy strands, these conductors provide superior corrosion resistance and high tensile strength, making them ideal for overhead power transmission and distribution lines. The AAAC conductors deliver reliable performance in diverse environmental conditions, ensuring efficient and durable electrical infrastructure.

  • slide

AAAC-All Aluminum Alloy Conductors ASTM B 399


AAAC-ASTM B399

  • Shape of conductor Stranded circular
  • Sectional area 6AWG-1000MCM
  • Insulation N/A
  • Standard AAAC-ASTM B399


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

AAAC-All Aluminum Alloy Conductors ASTM B 399 Application

Used as bare overhead conductor for primary and secondary distribution. Designed for utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics.
(1)AAAC conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction.

(2)The aluminum alloy conductors are used in replace of single-layer ACSR conductors to reduce power loss in overhead distribution and transmission lines,when replacing the aluminum conductor steel reinforced , the AAAC can save 5-8% of the construction cost.

(3)AAAC referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to replace the conventional ACSR.

Standards:

ASTM B399 Standard

Construction

All Aluminum Alloy construction

All Aluminum Alloy construction

AAAC-All Aluminum Alloy Conductors ASTM B 399
AREA Stranding Wire Dia.
(mm)
Approx. overall diameter
(mm)
Weight
(kg/km)
Nominal Breaking Load
(kN)
Nom. DC resistance at 20 Deg.
(ohm/km)
Nominal
AWGorMCM
Actual
(mm2)
6 13.3 7 1.554 4.67 37 4.22 2.5199
4 21.15 7 1.961 5.89 58 6.71 1.5824
2 33.63 7 2.474 7.42 93 10.68 0.9942
1/0 53.48 7 3.119 9.36 148 16.97 0.6256
2/0 67.42 7 3.503 10.51 186 20.52 0.4959
3/0 85.03 7 3.932 11.8 234 25.86 0.3936
4/0 107.23 7 4.417 13.26 296 32.63 0.3119
250 126.66 19 2.913 14.57 349 38.93 0.2642
300 152.1 19 3.193 15.97 419 46.77 0.2199
350 177.35 19 3.447 17.24 489 52.25 0.1887
400 202.71 19 3.686 18.43 559 59.74 0.1650
450 228 19 3.909 19.55 629 67.19 0.1467
500 253.35 19 4.12 20.6 698 74.64 0.1321
550 278.6 37 3.096 21.67 768 83.80 0.1202
600 303.8 37 3.233 22.63 838 91.38 0.1102
650 329.25 37 3.366 23.56 908 97.94 0.1016
700 354.55 37 3.493 24.45 978 102.20 0.0944
750 380.2 37 3.617 25.32 1049 109.60 0.0880
800 405.15 37 3.734 26.14 1117 116.80 0.0826
900 456.16 37 3.962 27.73 1258 131.50 0.0733
1000 506.71 37 4.176 29.23 1399 146.10 0.0660