Halogen Free Wire H07Z1-K

Halogen-Free Wire H07Z1-K is a low-voltage flexible cable rated at 450/750V, featuring a copper (Cu) conductor. It is insulated with HFFR (Halogen-Free Flame Retardant) material, which provides excellent fire safety by reducing toxic smoke and corrosive gases in case of fire. This wire is designed for flexible wiring applications in industrial, commercial, and residential installations, where safety and environmental considerations are important. Its flexible construction makes it suitable for use in machinery, control panels, and other environments requiring durable, reliable electrical connections with high safety standards.

  • slide

Halogen Free Wire H07Z1-K


Low voltage 450/750 V flexible Cu conductor, HFFR insulated

  • Conductor Material Copper
  • Insulation HFFR
  • Voltage 450/750V
  • Package 100 meters one roll


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

H07Z1-K Wire Application

For wiring of lamps, devices, switchgear cabinetsand distribution boxes. For installation in tubes,on, in and under plaster as well as in closed installation ducts. In building with a high density of people or valuable assets. For use in dry rooms.

H07Z1-K Wire Standard

Basic design to BS EN 50525-3-31

CONSTRUCTION :

H07Z1-K Wire Construction
Conductor : Copper conductor according to BS EN 60228 class 5.

H07Z1-K : 1.5-240mm2 Class 5 stranded copper conductor to BS EN 60228.

Insulation : Halogen-free thermoplastic compound, of type TI 7 to EN 50363-7

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

TECHNICAL :

CPR class: B2ca-s1,d1,a1
Test voltage: 2,5 kV
Rated voltage: 450/750 V
Bending radius (min): 5D
Min. laying temperature: 5°C
Ambience temp. range: -35°C to 35°C
Max. conductor temperature: 70°C
Max. short-circuit temperature:160°C

PARAMETER
NOMINAL CROSS-SECTION MAX. RESISTANCE AT 20°C CURRENT
CAPACITY IN THERMO ISOLATED WALL AT 30°)
CURRENT
CAPACITY IN ELECTRO INSTALLATION PIPE AT 30°)
CURRENT
CAPACITY ON THE WALL AT
30°)
INSULATION THICKNESS OUTER DIAM. (APPROX.) METAL WEIGHT CABLE WEIGHT (APPROX.)
mm² Ω/km A A A mm mm kg/km kg/km
    2 cores 3 cores 2 cores 3 cores 2 cores 3 cores   MIN MAX    
1x1,5 13,3 19 17 23 20 24 22 0,7 2,8 3,5 14,4 22
1x2,5 7,98 26 23 31 28 33 30 0,8 3,4 4,3 24,0 34
1x4 4,95 35 31 42 37 45 40 0,8 3,9 4,9 38,4 51
1x6 3,30 45 40 54 48 58 52 0,8 4,4 5,5 57,6 72
1x10 1,910 61 54 75 66 80 71 1,0 5,7 7,1 96,0 119
1x16 1,210 81 73 100 88 107 96 1,0 6,7 8,4 153,6 181
1x25 0,780 106 95 133 117 138 119 1,2 8,4 10,6 240,0 280
1x35 0,554 131 117 164 144 171 147 1,2 9,7 12,1 336,0 383
1x50 0,386 158 141 198 175 209 179 1,4 11,5 14,4 480,0 545
1x70 0,272 200 179 235 222 269 229 1,4 13,2 16,6 672,0 747
1x95 0,206 241 216 306 269 328 278 1,6 15,1 18,8 912,0 1012
1x120 0,161 278 249 354 312 382 322 1,6 16,7 20,9 1152,0 1263
1x150 0,129 318 285 393 342 441 371 1,8 18,6 23,3 1440,0 1579
1x185 0,106 362 324 449 384 506 424 2,0 20,6 25,8 1776,0 1948
1x240 0,0801 424 380 528 450 599 500 2,2 23,5 29,4 2304,0 2519