1-Ayky Cable

This Ayky power cable is rated at 0.6/1 kV, featuring aluminum conductors, with PVC insulation and sheathing. It provides reliable electrical transmission suitable for various industrial and distribution applications. The PVC insulation and sheath offer excellent insulation, mechanical protection, and weather resistance, ensuring safe and efficient operation in different environments. Its lightweight and flexible design make it easy to install, making it an ideal choice for building, distribution, and industrial equipment installations.

  • slide

1-Ayky Cable


Power cable 0,6/1 kV with Al conductors, PVC insulated and sheathed

  • Rated Voltage 0.6/1kV
  • Conductor Material Aluminum
  • Insulation Material PVC
  • Sheath PVC
  • Package Export wooden drum


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

1-Ayky Cable Application
Power distribution cables in power stations, industrial installations and switchgear, as well as in local mains. For fixed installation in interior premises, cable ducts, in the open air, in water as permitted by the local building regulations if no risk of any mechanical damage is to be expected.
1-Ayky Cable Standard
HD 603 S1, PNE 34 7659-3
CONSTRUCTION :
1-AYKY Cable Construction
Conductors: Al, class 1 or 2 according to EN 60228
Insulation: PVC compound DIV 1
Bedding: Extruded elastomere or plastomere compound or plastic tape
Sheath: PVC compound DMV 1
TECHNICAL :
Rated voltage: 0.6/1 kV
Test voltage: 4000 Veff
Temperature range:
Laying temperature: Min. 5 ° C
Operating temperature: 50 ° C to +70 ° C
Conductor temperature: Max. +70 ° C
Short-circuit temperature: Max. +160 ° C/5 s

Bending radius (min. ): 15 x of cable
Core identification: Coloured (HD 308 S2)
Fire properties:
Flame retardant (EN 50265-2-1, IEC 60332-1)

PARAMETER :

Number of cores x nominal cross section

Max. conductor resistance

Current ra- ting in the ground1)

Current rating in the air

Outer diameter 

Metal weight

weight

(mm2)

(Ω/km)

(A)

(A)

(mm)

(kg/km)

(kg/km)

1-AYKY

4 x 25 RE

1.238

103

78

22.4

300

750

5 x 25 RE

1.238

103

78

24.4

375

880

3 x 35 + 25 RE/RE

0.885/1.238

125

96

24.7

390

909

4 x 35 RE

0.885

125

96

24.7

420

939

5 x 35 RE

0.885

125

96

27.1

525

1,108

3 x 50 + 35 RE/RE

0.641/0.885

147

117

28.9

505

1,219

4 x 50 RE

0.641

147

117

28.9

600

1,275

4 x 50 SM

0.641

147

117

30.4

600

1,089

4 x 70 RE

0.443

183

150

32.2

840

1,618

3 x 70 + 50 RE/RE

0.443/0.641

183

150

32.2

780

1,559

3 x 70 + 50 SM/RM

0.443/0.641

183

150

33.6

780

1,314

4 x 70 RM

0.443

183

150

35.4

840

1,814

4 x 70 SM

0.443

183

150

33.6

840

1,345

3 x 95 + 70 SM/RM

0.326/0.443

216

182

39.3

1,065

1,743

4 x 95 SM

0.326

216

182

39.3

1,140

1,836

3 x 120 + 70 SM/RE

0.258/0.443

245

212

40.6

1,290

2,000

3 x 120 + 70 SM/RM

0.258/0.443

245

212

43.0

1,290

2,057

4 x 120 SM

0.258

245

212

43.0

1,440

2,225

3 x 150 + 70 SM/RE

0.206/0.443

278

245

45.6

1,560

2,415

3 x 150 + 70 SM/RM

0.206/0.443

278

245

46.8

1,560

2,457

4 x 150 SM

0.206

278

245

46.8

1,800

2,734

3 x 185 + 95 SM/RE

0.167/0.326

313

280

48.4

1,950

2,950

3 x 185 + 95 SM/RM

0.167/0.326

313

280

49.8

1,950

3,009

3 x 185 + 95 SM/SM

0.167/0.326

313

280

48.4

1,950

2,993

4 x 185 SM

0.167

313

280

49.8

2,220

3,364

3 x 240 + 120 SM/RE

0.129/0.258

359

330

54.8

2,520

3,728

3 x 240 + 120 SM/RM

0.129/0.258

359

330

56.4

2,520

3,804

4 x 240 SM

0.129

359

330

56.4

2,880

4,217