E-AY2Y Cable Application
Power distribution cables in power stations, industrial installations and switchgears, as well as in local mains.
For fixed installation undergroud, in interior premises, cable ducts, in open air, in water – as permited by the local building regulations – under severe mechanical stressing during installation and operation.
E-AY2Y Cable Standard
HD 603 S1, IEC 60502-1, ÖVE E8200-603
CONSTRUCTION :
E-AY2Y Cable Construction
1.Conductor - Aluminium conductor class 1 or class 2
2.Insulation - Core insulation of polyvinylchloride (PVC)
3.Filling - PVC core covering (FM) or taping (BD)
4.Outher sheath - Polyethylene (HDPE), Black, UV resistant
TECHNICAL :
Electrical Performance:
Nominal Voltage: 600/1000 Volt
Test Voltage [V]AC 4000
Short circuit time max. [sec] 5
Bending radius: x diameter 15
Temperature range:
Min. temp. for cable laying: -5°C
Max. working temperature: 70°C
Max. short-circuit temperature: 160°C
Min. bending radius: single-core – 15D; multicore – 12D
Flammability: Reaction to fire EN 60332-1-2 - Eca
PARAMETER :
Number of cores x Cross-section |
Overall diameter |
Weight |
Maximum electrical resistanceat 20℃ |
1x120 RM |
19 |
520 |
0.253 |
1x150 RM |
22 |
630 |
0.206 |
1x185 RM |
25 |
750 |
0.164 |
1x240 RM |
27 |
980 |
0.125 |
1x300 RM |
29 |
1200 |
0.1 |
3x240 SM + 120 SM |
55 |
3900 |
0.125 / 0.253 |
4x16 RM |
21 |
550 |
1.91 |
4x25 RM |
24 |
780 |
1.2 |
4x25 RE |
22 |
720 |
1.2 |
4x35 RM |
26 |
790 |
0.868 |
4x35 SM |
25 |
730 |
0.868 |
4x50 SM |
28 |
1100 |
0.641 |
4x50 SE |
26 |
1000 |
0.641 |
4x70 SM |
31 |
1350 |
0.443 |
4x70 SE |
30 |
1210 |
0.443 |
4x95 SM |
36 |
1800 |
0.32 |
4x95 SE |
34 |
1720 |
0.32 |
4x150 SM |
43 |
2700 |
0.206 |
4x150 SE |
41 |
2580 |
0.206 |
4x185 SM |
47 |
3080 |
0.164 |
4x185 SE |
46 |
2930 |
0.164 |
4x240 SE |
53 |
4140 |
0.125 |
4x240 SM |
54 |
4200 |
0.125 |
4x300 SM |
60 |
4630 |
0.1 |