Cable Application
SE-N1XE-AS is a halogen free, XLPE-insulated, PE-sheathed cable with sector shaped, stranded aluminium conductors. The cable is designed according to HD 603.The conductors have resistance and number of wires according to SS-EN 60228 class 2. The cores are identified by colours according to HD 308. The cable may be used for fixed installation outdoors in air, ground and water.
Cable Standards:
SS 424 14 18, HD 603
CONSTRUCTION :
Cable Construction
Conductor: Class 2 stranded Aluminium Conductor
Insulation: XLPE insulation
Sheath: PE outer sheath
TECHNICAL DATA :
Voltage Rating Uo/U (Um) 0.6/1 (1.2)kV
Test Voltage:3.5kV for 5 Minutes
Temperature Rating:-20°C to +90°C
Maximum Short Circuit Temperature:+250°C (max 5 seconds)
Environment temperature should be no lower than 0°C for laying the cable.
Minimum Bend Radius:
Bending factor when installed: 8 x overall diameter
Bending factor when laying: 12 x overall diameter
Installation type:Outdoor - Direct burial
PARAMETER :
Name | Cross Section Area | Nominal outer diameter | Approx Weight |
mm2 | mm | kg/100m | |
SE-N1XE-AS 1 kV 4G240 | 240 | 54 | 345 |
SE-N1XE-AS 1 kV 4G150 | 150 | 43 | 215 |
SE-N1XE-AS 1 kV 4G95 | 95 | 35 | 140 |
SE-N1XE-AS 1 kV 4G50 | 50 | 27 | 77 |