Cable NA2XY Double Application
General use as power cable. In low voltage distribution networks, industrial installations, buildings and operating centers. For fixed installations, in indoor areas (trays, ducts), in underground ducts or buried direct in ground, in dry or wet locations.
Cable NA2XY Double Standards:
National : NTP-IEC 60228; NTP-IEC 60502-1
International : IEC 60228; IEC 60332-1; IEC 60332-3-24 Cat.C; IEC 60502-1; IEC 60684-2; IEC 60754-2; IEC 60811-1-1; IEC 60811-1-2; IEC 60811-1-3; IEC 60811-1-4; IEC 60811-2-1; IEC 60811-3-1; IEC 61034
CONSTRUCTION :
Cable NA2XY Double Construction
1. Conductor: Compact aluminium 1350, class 2.
2. Insulation: Cross linked polyethylene XLPE.
3. Outer sheath: Polyvinyl chloride PVC
4. Tape: Polyester tape.
Colour:
Insulation: Natural.
Outer sheath: White Black.
TECHNICAL DATA :
Main characteristics:
Good electrical and mechanical properties. Cross-linked polyethylene insulation allows greater power capacity under any operating condition, minimum dielectric losses, high insulation resistance. The PVC outer sheath allows an adequate resistance to greases, oils, abrasion and sunlight. Flame retardant.
Rated voltage:0.6/1kV
Test voltage:3.5kV A.C.
Maximum conductor temperature : 90°C.
Maximum operating temperature:130 °C
Short-circuit max. conductor temperature:250 °C
PARAMETER :
NA2XY DOUBLE CABLES Design Parameters
No. Conductor x Section No x mm2 |
Minimum number of wires | Insulation thickness mm | Sheath thickness mm | Outside diameter mm | Nominal Weight kg/km | |||
2-1x10 | 1 | 0.7 | 1.4 | 8x16 | 150 | |||
2-1x16 | 6 | 0.7 | 1.4 | 9x18 | 212 | |||
2-1x25 | 6 | 0.9 | 1.4 | 11x21 | 300 | |||
2-1x35 | 6 | 0.9 | 1.4 | 11x23 | 360 | |||
2-1x50 | 6 | 1.0 | 1.4 | 13x26 | 480 |