NA2XY Cable Single Core Unipolar 0.6/1 kV

The NA2XY cable is a single-core (unipolar) power cable rated for 0.6/1 kV. It is designed for fixed electrical installations, providing reliable power transmission. Typically, it features XLPE insulation for high thermal and electrical performance, with a protective outer sheath (often PVC) to shield against mechanical damage, moisture, and environmental factors. Suitable for industrial and infrastructure applications where a single-core power cable is required.

  • slide

NA2XY Cable Single Core Unipolar 0.6/1 kV


NA2XY Unipolar

  • Rated Voltage 0.6/1kV
  • Conductor Material Aluminium 1350, class 2
  • Insulation Material XLPE
  • Sheath PVC
  • Number of cores Unipolar
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

Cable NA2XY Unipolar Application

General use as power cable. In low voltage distribution networks, industrial installations, buildings and operating centers. For fixed installations, in indoor areas (trays, ducts), in underground ducts or buried direct in ground, in dry or wet locations.
Cable NA2XY Unipolar Standards:

National : NTP-IEC 60228; NTP-IEC 60502-1

International : IEC 60228; IEC 60332-1; IEC 60332-3-24 Cat.C; IEC 60502-1; IEC 60684-2; IEC 60754-2; IEC 60811-1-1; IEC 60811-1-2; IEC 60811-1-3; IEC 60811-1-4; IEC 60811-2-1; IEC 60811-3-1; IEC 61034
CONSTRUCTION :
Cable NA2XY Triple Construction

1. Conductor: Compact aluminium 1350, class 2.

2. Insulation: Cross linked polyethylene XLPE.

3. Outer sheath: Polyvinyl chloride PVC

Colour:

Insulation: Natural.

Outer sheath: Black
TECHNICAL DATA :
Main characteristics:

The cable has excellent electric properties. The cross-linked polyethylene insulation allows a higher power capacity current under any operation conditions, lower dielectric losses, high insulation resistance. The outer sheath has the following characteristics: Fire retardant, low emission dense smoke and halogen free. Sunlight resistance.

Rated voltage:0.6/1kV
Test voltage:3.5kV A.C.
Maximum conductor temperature : 90°C.
Maximum operating temperature:130 °C

Short-circuit max. conductor temperature:250 °C

PARAMETER :
NA2XY Unipolar Parameters

No. of cores and nominal cross section Thickness of Insulation  Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
1X10 0.7 1.4 8.0 75 3.08 55 71
1X16 0.7 1.4 9.0 106 1.91 71 91
1X25 0.9 1.4 10.6 150 1.20 94 115
1X35 0.9 1.4 11.6 180 0.868 115 140
1X50 1.0 1.4 13.1 240 0.641 140 165
1X70 1.1 1.4 15.0 320 0.443 180 205
1X95 1.1 1.5 16.8 400 0.320 220 245
1X120 1.2 1.5 18.4 500 0.253 260 280
1X150 1.4 1.6 20.5 600 0.206 300 315
1X185 1.6 1.6 22.6 730 0.164 350 360
1X240 1.7 1.7 25.2 930 0.125 414 420
1x300 1.8 1.8 27.8 1140 0.100 485 475
1x400 2.0 1.9 31.4 1500 0.0778 570 545
1x500 2.2 2.0 34.9 1800 0.0605 670 620
1X630 2.4 2.2 39.1 2285 0.0469 790 705