NA2XY Cable Triple 0.6/1kv

The NA2XY cable with triple cores rated at 0.6/1kV is a three-conductor (phase, neutral, and possibly a protective conductor) cable designed for electrical power distribution at voltages up to 1 kV. It typically features XLPE insulation for high thermal and electrical performance, with an outer sheath (like PVC) for mechanical protection. Such cables are commonly used in industrial or infrastructure settings for three-phase power systems.

  • slide

NA2XY Cable Triple 0.6/1kv


NA2XY Triple

  • Rated Voltage 0.6/1kV
  • Conductor Material Aluminium 1350, class 2
  • Insulation Material XLPE
  • Sheath PVC
  • Number of cores Triple
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

Cable NA2XY Triple Application

General use as power cable. In low voltage distribution networks, industrial installations, buildings and operating centers. For fixed installations, in indoor areas (trays, ducts), in underground ducts or buried direct in ground, in dry or wet locations.
Cable NA2XY Triple Standards:

National : NTP-IEC 60228; NTP-IEC 60502-1

International : IEC 60228; IEC 60332-1; IEC 60332-3-24 Cat.C; IEC 60502-1; IEC 60684-2; IEC 60754-2; IEC 60811-1-1; IEC 60811-1-2; IEC 60811-1-3; IEC 60811-1-4; IEC 60811-2-1; IEC 60811-3-1; IEC 61034
CONSTRUCTION :
Cable NA2XY Triple Construction

1. Conductor: Compact aluminium 1350, class 2.

2. Insulation: Cross linked polyethylene XLPE.

3. Outer sheath: polyvinyl chloride PVC

4. Tape: Polyester tape.

Colour:

Insulation: Natural.

Outer sheath: White, black, and red, or white and black.
TECHNICAL DATA :
Main characteristics:

The cable has excellent electric properties. The cross-linked polyethylene insulation allows a higher power capacity current under any operation conditions, lower dielectric losses, high insulation resistance. The outer sheath has the following characteristics: Fire retardant, low emission dense smoke and halogen free. Sunlight resistance.

Rated voltage:0.6/1kV
Test voltage:3.5kV A.C.
Maximum conductor temperature : 90°C.
Maximum operating temperature:130 °C

Short-circuit max. conductor temperature:250 °C

PARAMETER :
NA2XY TRIPLE CABLES Design Parameters

No. Conductor x Section No x mm2 Minimum number of wires Insulation thickness mm Sheath thickness mm Outside diameter mm Nominal Weight kg/km
3-1x16 6 0.7 1.4 9.0x27.2 318
3-1x25 6 0.9 1.4 10.6x31.8 450
3-1x35 6 0.9 1.4 11.6x34.7 540
3-1x50

6 1.0 1.4 13.1x39.3 720
3-1x70 12 1.1 1.4 15.0x45 960
3-1x95

15 1.1 1.5 16.8x50.4 1200
3-1x120 18 1.2 1.5 18.4x55.2 1500
3-1x150

18 1.4 1.6 20.5x61.6 1800
3-1x185

30 1.6 1.6 22.6x67.8 2190
3-1x240 34 1.7 1.7 25.2x75.6 2790
3-1x300

34 1.8 1.8 27.8x83.5 3420
3-1x400 53 2.0 1.9 31.4x94.3 4500
3-1x500

53 2.2 2.0 34.9x104.7 5400