U-1000 RVFV XAV Cable

These U-1000 RVFV cables are suitable for direct burial without additional protection or for installation on cable trays or in ducts where mechanical protection is necessary

  • U 1000 Rvfv Xav Cable

U-1000 RVFV XAV Cable


Power Cable 0,6/1 kV with Cu conductors, XLPE insulated and Double Steel Tape Armoured

  • Rated Voltage 0.6/1kV
  • Conductor Material copper
  • Insulation Material Cross-linked polyethylene (XLPE)
  • Sheath PVC
  • Armour Double Galvansied Steel Tape


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

U-1000 RVFV XAV Cable Application

These U-1000 RVFV cables are suitable for direct burial without additional protection or for installation on cable trays or in ducts where mechanical protection is necessary

U-1000 RVFV XAV Cable Standard:

NF C 32-322
Flame Retardant according to NF C 32-070 C2, IEC 60332-1-2

CONSTRUCTION :
U-1000 RVFV XAV Cable Construction

Conductor: 1.5mm² to 4mm²: Class 1 solid copper conductor
6mm² and above: Class 2 stranded copper conductor
Class 2 stranded conductor available for these sizes on request

Insulation: Cross-linked polyethylene (XLPE) insulation type XLPE according to IEC 60502-1.

Armour bedding: Black extruded PVC separation sheath.
Armour: Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. Steel tape is used in the multicore cables.

Outer sheath: Flexible PVC outer sheath, Black colour.

The standard identification of insulated conductors is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Green/Yellow
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Green/Yellow
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Green/Yellow
6 or more Black numbered + Green/Yellow

CHARACTERISTICS :U-1000 RVFV XAV Cable Characteristics

Electrical performance: Low voltage 0,6/1kV.
Thermal performance:
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance:
Flame non-propagation according to EN 60332-1 and IEC 60332-1.
Reduced halogen emission. Chlorine <15%.
Reaction to fire CPR: Eca, according to EN 50575.
Mechanical performance:
Minimum bending radius: x5 cable diameter.
Impact resistance: AG2 Medium severity.
Environmental performance
Chemical & Oil resistance: Good.
UV Resistant: UNE 211605.
Installation conditions
Open Air.
Buried.
In conduit.

Other
Meter by meter marking.

PARAMETER :

CROSS SECTION MM2INSULATION THICKNESS MMAMOUR THICKNESS MMMINIMUM SHEATH THICKNESS MMMAXIMUM OVERALL DIAMETER MMAPPROX CABLE WEIGHT KG/KM
2x1.50.70.21.311.5230
2x2.50.70.21.312.5275
2x40.70.21.413.5330
2x60.70.21.415.5430
2x100.70.21.416.5555
2x160.70.21.519770
2x250.90.21.622.51080
2x350.90.21.7251390
3x1.50.70.21.312255
3x2.50.70.21.313305
3x40.70.21.414380
3x60.70.21.416500
3x100.70.21.517.5665
3x160.70.21.520930
3x250.90.21.6241325
3x350.90.21.726.51720
3x500.90.21.8292125
3x701.10.2234.53080
3x951.10.52.1404505
3x1201.20.52.344.55540
3x1501.40.52.448.56655
3x1851.60.52.553.58150
3x2401.70.52.76110575
3x3001.80.52.966.513055
3x50+351.0/090.21.9332730
3x70+501.1/0.90.22363440
3x95+501.1/1.00.52.242.55080
3x120+701.2/1.10.52.346.56275
3x150+701.4/1.10.52.5507340
3x185+701.6/1.10.52.6568975
3x240+951.7/1.10.52.862.511435
4x1.50.70.21.313290
4x2.50.70.21.414355
4x40.70.21.415440
4x60.70.21.417585
4x100.70.21.519800
4x160.70.21.6221120
4x250.90.21.7261650
4x350.90.21.8292135
4x5010.21.932.52745
4x701.10.52.1394295
4x951.10.52.344.55660
4x1201.20.52.448.56880
4x1501.40.52.6538315
4x1851.60.52.760.510510
4x2401.70.52.96713370
4x3001.80.53.17316360
Need Help?