Quick Answer
Yes, you CAN run Romex (NM-B cable) inside conduit according to the National Electrical Code (NEC). However, it's often not the most practical or cost-effective choice for most installations.
The NEC does not prohibit running NM-B cable through conduit for physical protection. But there are important considerations about when it makes sense and when you should use individual THHN wires instead.

Can You Run Romex in Conduit
Understanding the Code Requirements
What the NEC Says
The National Electrical Code (NEC Article 334) allows NM-B cable (Romex) to be run through conduit when additional protection is needed. There is no blanket prohibition against this practice.
Key NEC provisions:
- NM-B cable can be installed in conduit for physical protection
- Standard conduit fill calculations apply
- The cable must be suitable for the environment
- All standard NM-B installation rules still apply
Common Misconceptions
Many electricians and DIYers believe running Romex in conduit is 'against code.' This myth likely stems from:
- Inefficiency - It's rarely the best method, so experienced electricians avoid it
- Regional practices - Some jurisdictions have local amendments
- Commercial restrictions - NM-B is prohibited in commercial buildings (regardless of conduit)
- Conduit fill issues - Romex's oval shape makes calculation complex
When Running Romex in Conduit Makes Sense
✅ Good Reasons to Use Romex in Conduit
1. Short Physical Protection Runs
- Protecting exposed cable in a garage (below 8 feet)
- Running through a crawl space prone to damage
- Crossing a mechanical room with equipment
- Length: Usually under 6 feet
2. Already Installed Romex Needs Protection
Example: You have existing Romex running along a basement
wall, but now need to protect it due to finished space
or new code requirements.
Solution: Add surface-mounted conduit over the existing
Romex rather than rewiring.
3. Temporary Protection During Construction
- Protecting installed wiring during framing
- Safeguarding circuits before drywall installation
- Can be removed after construction
4. Single Circuit in Existing Conduit System
- You already have empty conduit runs
- Only need to add one circuit
- Short distance makes THHN overkill
5. Attic or Crawl Space Protection
- Protecting cable where it crosses open areas
- Preventing accidental damage during storage
- Areas with potential foot traffic
❌ When NOT to Run Romex in Conduit
1. Long Conduit Runs
- Over 10-15 feet of conduit
- Multiple bends or turns
- Difficult to pull Romex through
- Better choice: Individual THHN wires
2. Multiple Circuits
- Running several circuits in one conduit
- Romex bundles poorly
- Takes up excessive space
- Better choice: Multiple THHN wires sharing conduit
3. Wet or Damp Locations
- Even in conduit, standard NM-B isn't rated for wet locations
- Moisture can enter conduit ends
- Better choice: THWN/THHN wires or UF cable
4. Outdoor Installations
- NM-B not rated for outdoor use
- Temperature fluctuations cause problems
- Better choice: UF cable or individual THHN in conduit
5. Underground Runs
- NM-B cannot be buried
- Even PVC conduit doesn't change this
- Better choice: UF cable or THHN in Schedule 40 PVC
6. Commercial Buildings
- NEC prohibits NM-B in most commercial occupancies
- Conduit doesn't change this restriction
- Must use: MC cable, AC cable, or THHN in conduit
Romex vs THHN in Conduit: Direct Comparison
Space Efficiency
| Wire Type | 3/4' EMT Capacity | 1' EMT Capacity |
|---|---|---|
| 12/2 Romex | 1 cable maximum | 2 cables maximum |
| 12 AWG THHN | 9 wires (3 circuits) | 16 wires (5+ circuits) |
| 10/2 Romex | 1 cable maximum | 1-2 cables |
| 10 AWG THHN | 6 wires (2 circuits) | 10 wires (3 circuits) |
THHN wins dramatically for space efficiency.
Cost Comparison (100-foot run)
Romex in Conduit:
- 100 ft of 12/2 Romex: $45-60
- 100 ft of 3/4' EMT: $40-50
- Fittings and connectors: $20-30
- Total: $105-140
THHN in Conduit:
- 100 ft each of 12 AWG THHN (3 wires): $60-75
- 100 ft of 3/4' EMT: $40-50
- Fittings and connectors: $20-30
- Total: $120-155
Winner: Romex costs slightly less, but THHN offers more flexibility.
Installation Difficulty
Romex in Conduit:
- ❌ Stiff and hard to pull through bends
- ❌ Oval shape catches on fittings
- ❌ Limited to very short runs
- ❌ Cannot easily add circuits later
- ✅ Pre-assembled (no individual wires)
THHN in Conduit:
- ✅ Round wires pull easily
- ✅ Works for long runs
- ✅ Can add circuits later if space allows
- ✅ Better for multiple bends
- ❌ Must pull three separate wires
Future Flexibility
Romex: No future flexibility. The circuit is fixed.
THHN: Can potentially add circuits later if conduit has extra capacity.
Conduit Fill Requirements for Romex
NEC Chapter 9 Fill Calculations
When running NM-B cable in conduit, you must follow Table 1 (percentage fill) and Table 4 (conduit dimensions) plus the cable's actual cross-sectional area.
Maximum Fill Percentages:
- 1 cable: 53% fill
- 2 cables: 31% fill
- 3+ cables: 40% fill
Common Romex Sizes in Conduit
14/2 Romex (0.0514 sq. in.):
- 1/2' EMT: 1 cable maximum
- 3/4' EMT: 2 cables maximum
- 1' EMT: 4 cables maximum
12/2 Romex (0.0719 sq. in.):
- 1/2' EMT: 1 cable maximum
- 3/4' EMT: 2 cables maximum
- 1' EMT: 3 cables maximum
10/2 Romex (0.1041 sq. in.):
- 1/2' EMT: 1 cable maximum
- 3/4' EMT: 1 cable maximum
- 1' EMT: 2 cables maximum
10/3 Romex (0.1333 sq. in.):
- 1/2' EMT: Cannot fit
- 3/4' EMT: 1 cable maximum
- 1' EMT: 2 cables maximum
Fill Calculator Rule of Thumb
For quick field calculations:
Romex fits if: Cable area × Number of cables ≤ (Conduit area × Fill %)
Example: Two 12/2 Romex in 3/4' EMT
- Cable area: 0.0719 sq. in. each
- Conduit area: 0.533 sq. in.
- Fill limit (2 cables): 31%
Calculation: 0.0719 × 2 = 0.144
0.533 × 0.31 = 0.165
0.144 < 0.165 ✓ FITS
Installation Tips for Romex in Conduit
1. Keep Runs Short and Straight
Ideal: Straight runs under 6 feet Maximum practical: 10 feet with one 90° bend Avoid: Multiple bends or long distances
2. Use Larger Conduit Than Calculated
Even if calculations say 1/2' works, use 3/4' minimum. The extra space makes pulling dramatically easier.
3. Pull Wire Lubricant
Use pulling compound on the Romex jacket:
- Apply generously at conduit entry
- Helps the oval cable slide through
- Especially important for bends
Recommended products:
- Ideal Yellow 77
- Klein Tools Wire Pulling Lubricant
- Polywater J (general purpose)
4. Support Before and After Conduit
NM-B cable must be supported within 12 inches of entering/exiting conduit, then every 4.5 feet along its run.
[Cable staple] → 12' max → [Conduit entry]
[Protected run inside conduit]
[Conduit exit] → 12' max → [Cable staple]
5. Avoid Sharp Bends Inside Conduit
- Use sweep elbows, not close-radius elbows
- Maintain minimum bend radius (5× cable diameter)
- Never kink or twist the Romex
6. Seal Conduit Ends in Damp Areas
Even though Romex isn't rated for wet locations, sealing conduit ends prevents moisture infiltration:
- Use duct seal putty at terminations
- Prevents condensation entry
- Especially important in crawl spaces
7. Consider Using Pulling Grip
For longer runs or multiple cables:
1. Attach pulling grip to Romex end
2. Feed pull string through conduit first
3. Attach string to grip
4. Pull cable through steadily
5. Have helper feed cable at entry point
Alternative Solutions to Consider
Option 1: Switch to THHN Wires
When it's better: Any run over 10 feet or with multiple bends
How to convert:
- Replace 12/2 Romex with: 12 AWG THHN black, white, green
- Replace 10/3 Romex with: 10 AWG THHN black, red, white, green
- Pull all wires together through conduit
Advantages:
- Much easier to pull
- Works for long runs
- Can add circuits later
Option 2: Use MC Cable (Metal-Clad)
When it's better: Exposed areas needing physical protection
Characteristics:
- Similar to Romex but with metal armor
- Can be used exposed in many locations
- Doesn't require conduit for protection
- More expensive than Romex
Best for:
- Basements and garages
- Exposed commercial runs
- Areas requiring mechanical protection
Option 3: Surface-Mount Raceway
When it's better: Finished walls where you need protection
Types:
- Plastic raceway (Wiremold)
- Metal raceway
- Easy to install on surfaces
- Can run Romex inside
Best for:
- Garage workshops
- Basement remodels
- Adding circuits to finished spaces
Option 4: Use Proper Cable for Location
Instead of forcing Romex into conduit for environmental protection, use cable rated for the condition:
| Location | Use This | Not This |
|---|---|---|
| Outdoor above ground | THWN in conduit | Romex in conduit |
| Underground | UF cable or THWN in Sch 40 | Romex in conduit |
| Wet basement | THWN in conduit | Romex in conduit |
| Damp crawlspace | UF or THWN | Romex in conduit |
Special Situations
Romex Through Concrete Slab
Question: Can I run Romex in conduit embedded in concrete?
Answer: No. NEC 334.12(B)(4) prohibits NM-B cable embedded in concrete, cement, or aggregate, even inside conduit.
Solution: Use Schedule 40 PVC with THHN wires or UF cable (not in conduit).
Romex in PVC Conduit Outdoors
Question: Can I protect outdoor Romex by putting it in PVC conduit?
Answer: No. NM-B is not rated for outdoor use. The conduit doesn't change the cable's rating.
Solution:
- Use UF cable (no conduit needed for direct burial)
- Or use THWN wires in Schedule 40 PVC
- Or use weatherproof conduit with THHN/THWN
Romex From House to Detached Garage
Question: Can I run Romex in underground conduit between buildings?
Answer: No. Even in conduit, NM-B cannot be used:
- Underground (NEC 334.12(B)(4))
- In wet locations (conduit can have moisture)
- For outside wiring (NEC 334.12(B)(2))
Solution:
- Direct burial: Use UF cable
- In conduit: Use THWN wires in Schedule 40 PVC
Romex in Attic with Conduit Protection
Question: I have Romex running across an attic floor. Can I add conduit over it?
Answer: Yes, this is one of the best uses for Romex in conduit:
- Protects against foot traffic
- Prevents accidental damage
- Can use surface-mount conduit
- Short runs make installation easy
Best practice:
- Use 3/4' or 1' EMT or PVC
- Secure conduit every 3 feet
- Support Romex before/after conduit
Why Do Electricians Say 'You Can't Do That'?
If running Romex in conduit is code-compliant, why do many electricians say it's wrong?
Reason 1: It's Inefficient
Professional electricians avoid Romex in conduit because:
- Takes longer to install
- More difficult to pull
- Wastes conduit space
- Not cost-effective for most jobs
Their perspective: 'We CAN do it, but we WON'T because it's bad practice.'
Reason 2: Local Amendments
Some jurisdictions have local code amendments that restrict NM-B cable more than the NEC:
- Some cities require conduit for all wiring
- Some prohibit NM-B in basements entirely
- Some have stricter protection requirements
Always check your local code.
Reason 3: Commercial Work
Electricians who primarily work commercial may say 'you can't use Romex in conduit' because:
- NM-B is prohibited in commercial buildings
- This is true regardless of conduit
- They're thinking of commercial code restrictions
In residential: Different rules apply.
Reason 4: Professional Standards
Many electricians follow higher standards than minimum code:
- Use MC cable instead of Romex
- Run individual wires in conduit
- Avoid mixing methods
Their view: 'Just because it's legal doesn't mean it's professional.'
Common Mistakes to Avoid
❌ Mistake 1: Exceeding Conduit Fill
Error: Forcing too many Romex cables into conduit
Why it's wrong:
- Difficult or impossible to pull
- Damages cable insulation
- Violates NEC fill calculations
- Can cause overheating
Solution: Use larger conduit or switch to THHN wires
❌ Mistake 2: Long Runs with Multiple Bends
Error: Trying to pull Romex through 30 feet of conduit with three 90° bends
Why it's wrong:
- Romex is too stiff for complex conduit runs
- Oval shape catches at every bend
- Risk of damaging conductors
Solution: Use THHN wires for any run over 10 feet or with 2+ bends
❌ Mistake 3: Using Wrong Romex for Location
Error: Running standard NM-B in conduit through wet basement
Why it's wrong:
- NM-B not rated for wet locations
- Conduit can have condensation inside
- Moisture damages cable over time
Solution: Use THWN wires rated for wet locations
❌ Mistake 4: Not Supporting Cable Properly
Error: Romex enters conduit but isn't secured within 12 inches
Why it's wrong:
- Cable can be pulled out of conduit
- Violates NEC 334.30 support requirements
- Creates strain on connections
Solution: Support within 12' of conduit entry/exit, then every 4.5 feet
❌ Mistake 5: Mixing Cable Types in Conduit
Error: Running Romex and THHN wires together in same conduit
Why it's wrong:
- Complicated fill calculations
- Different jacket materials
- Professional standards discourage mixing
Solution: Use all Romex or all individual wires, not both
Step-by-Step: Installing Romex in Conduit
Tools and Materials Needed
Tools:
- Measuring tape
- Conduit cutter or hacksaw
- Deburring tool or file
- Screwdriver (for connectors)
- Wire pulling lubricant
- Fish tape or pull string (for longer runs)
- Cable staples
Materials:
- EMT or PVC conduit (3/4' or 1' recommended)
- Conduit connectors/couplings
- Set-screw or compression connectors
- Romex cable (proper size for circuit)
- Support straps for conduit
Installation Process
Step 1: Plan the Route
1. Measure conduit path
2. Identify entry and exit points
3. Count number of bends needed
4. Confirm run is short enough for Romex
(Under 10 feet with minimal bends)
Step 2: Install Conduit
1. Cut conduit to length
2. Deburr cut ends (important!)
3. Install mounting straps every 3 feet
4. Attach conduit to structure
5. Install connectors at entry/exit boxes
Step 3: Prepare Cable
1. Cut Romex 12-18 inches longer than conduit
2. Leave extra length at both ends
3. Apply pulling lubricant to first 12 inches
4. Optional: Tape cable end to prevent snagging
Step 4: Pull Cable Through
For short straight runs:
1. Feed Romex into conduit by hand
2. Have helper push while you pull
3. Apply more lubricant if resistance increases
4. Pull steadily - don't jerk or yank
For longer or bent runs:
1. Feed fish tape through conduit first
2. Attach Romex to fish tape with pulling grip
3. Pull fish tape while helper feeds cable
4. Stop if excessive resistance felt
Step 5: Secure Cable
1. Leave 8-12 inches extending from each end
2. Secure Romex within 12' of conduit entry
3. Continue standard Romex installation rules
4. Support every 4.5 feet after conduit
Step 6: Make Connections
1. Strip cable sheathing at boxes
2. Strip wire insulation 3/4'
3. Make connections per normal practice
4. Install box covers
Real-World Scenarios
Scenario 1: Protecting Garage Wall Cable
Situation: Romex runs along a garage wall below 8 feet (impact zone)
Code requirement: Must be protected from physical damage
Solution:
- Install 3/4' EMT surface-mount conduit over existing Romex
- 6-foot section along wall
- Secure conduit with straps every 3 feet
- Much faster than rewiring with MC cable
Result: ✅ Code compliant, ✅ Cost effective, ✅ Quick install
Scenario 2: Crawl Space Beam Crossing
Situation: Romex must cross under steel beam in crawlspace
Problem: Exposed to potential damage from foot traffic
Solution:
- 4-foot section of 1' PVC protecting cable
- Strapped to beam underside
- Romex secured with staples before/after conduit
Result: ✅ Simple protection, ✅ No rewiring needed
Scenario 3: Finished Basement Addition
Situation: Adding circuit in finished basement, can't fish through walls
Poor choice: Surface-mount Romex in conduit (looks bad)
Better choice:
- Use Wiremold surface raceway (cleaner look)
- Or use MC cable (no conduit needed)
- Or use THHN in EMT (more professional)
Result: ❌ Romex in conduit works but better options exist
Scenario 4: Detached Shed Wiring
Situation: Running power from house to shed 40 feet away
Wrong approach: Romex in underground PVC (NOT allowed)
Correct approach:
- Direct bury UF cable 18-24 inches deep
- Or THWN wires in Schedule 40 PVC conduit
Result: ❌ Cannot use Romex for this application
Frequently Asked Questions
Can you run Romex and THHN together in the same conduit?
Technically yes per code, but it's not recommended:
- Complicated fill calculations
- Different insulation types
- Professional standards discourage it
- Choose one method or the other
Does running Romex in conduit require derating?
No additional derating for Romex in conduit if:
- You're running three current-carrying conductors or fewer
- Standard conduit fill limits are followed
- Ambient temperature is under 86°F
Multiple Romex cables in one conduit may require derating if you have 4+ current-carrying conductors.
Can I add more wires to conduit with Romex later?
Very difficult. Once Romex is installed in conduit:
- Hard to pull additional cables through
- Likely to exceed fill limits
- May need to remove everything and start over
This is a major disadvantage vs. THHN wires.
What if my local inspector says I can't do it?
Your local inspector has final authority:
- Some jurisdictions have amendments to NEC
- Local requirements supersede national code
- Always follow local inspector guidance
- Ask for specific code reference if denied
Is it better to use EMT or PVC conduit for Romex?
EMT (metal):
- ✅ Provides grounding path
- ✅ More durable above ground
- ❌ More expensive
- ❌ Cannot be buried without coating
PVC (plastic):
- ✅ Less expensive
- ✅ Easier to cut and work with
- ✅ Can be buried (Schedule 40)
- ❌ No grounding path
- ❌ Can become brittle with UV exposure
For protecting Romex in short runs, either works fine. Use EMT for exposed areas, PVC for hidden areas.
Can I use flexible conduit (Liquidtight) for Romex?
Yes, flexible conduit can be used with Romex:
- Good for short connections to equipment
- Easier to route around obstacles
- More expensive than rigid conduit
- Follow same fill calculations
Common use: Protecting Romex connection to garbage disposal or dishwasher.
Final Recommendations
When to Use Romex in Conduit
Use this method only when:
- Run is very short (under 6 feet ideal, 10 feet maximum)
- Minimal bends (one 90° bend maximum)
- Single circuit protection needed
- Romex is already installed and needs added protection
- Cost savings matter and run is simple
When to Use Alternatives
Choose THHN wires in conduit when:
- Run exceeds 10 feet
- Multiple bends required
- Multiple circuits needed
- Professional appearance important
- Wet or damp location
- Underground or outdoor installation
Choose MC cable when:
- Physical protection needed without conduit
- Exposed commercial installation
- Flexibility in routing required
- Local code requires armored cable
Choose UF cable when:
- Outdoor above-ground installation
- Underground direct burial
- Damp or wet locations without conduit
Conclusion
Yes, you can run Romex in conduit - it's completely legal per the National Electrical Code. But just because something is code-compliant doesn't mean it's the best solution for every situation.
Key takeaways:
- ✅ Legal: NEC allows NM-B cable in conduit
- ✅ Best for: Short protection runs under 10 feet
- ⚠️ Practical limits: Difficult to pull through long or bent runs
- ❌ Poor choice: Long runs, multiple circuits, wet locations
- 💡 Better alternatives often exist: THHN wires, MC cable, or UF cable
The myth that 'you can't run Romex in conduit' comes from the fact that it's rarely the best method, not because it's against code. Professional electricians avoid it because better options usually exist.
For your specific situation: If you have a short, straight run where you need to protect existing or new Romex, go ahead and use conduit. For anything more complex, consider using individual THHN wires in conduit instead.
Related articles:
