NS75/NS90 Quadruplex Unjacketed Overhead Neutral Supported Cable

The NS75/NS90 Quadruplex Unjacketed Overhead Neutral Supported Cable is an overhead distribution cable designed for electrical systems, typically used where a neutral conductor is supported separately from the phase conductors.

  • slide

NS75/NS90 Quadruplex Unjacketed Overhead Neutral Supported Cable


NS75/NS90 Quadruplex Unjacketed Overhead Neutral Supported Cable

  • Conductor Soft 1350-H19 Aluminum Conductor
  • Insulation Thermoplastic Polyethylene or Cross-linked Polyethylene
  • Voltage 600V
  • Number of cores Quadruplex
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

Quadruplex Unjacketed Overhead Neutral Supported Cable Description

The insulated conductors of NS75/NS90 Service Drop Cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. The cable is rated 600 V with a maximum conductor operating temperature of 90°C for Cross-linked Polyethylene insulation, which allows for higher ampacity compared to NS75 cable.

Quadruplex Unjacketed Overhead Neutral Supported Cable Application

Duplex and Triplex NS75/NS90 Service Drop Cable is intended to deliver single phase power from the secondary overhead power line or polemounted transformer to the service entrance conductors at the user’s building or other structure.
Quadruplex NS75/NS90 Service Drop Cable is intended to deliver three phase power from the secondary overhead power line or pole-mounted transformers to the service entrance conductors at the user’s building or other structure. NS75/NS90 cable may also be used as pole line secondary with service splices at the pole (also refer to CEC rule 12-318). NS75/NS90 cable is rated for use on systems having nominal voltages of 600 V or less.

Quadruplex Unjacketed Overhead Neutral Supported Cable Standards

NS75/NS90 cables meet or exceed the following standards
CSA C22.C No. 129
CSA listed NS75 & NS90
Sunlight resistant

Quadruplex Unjacketed Overhead Neutral Supported Cable Construction

Conductors: 2, 3, or 4 Aluminum alloy 1350-H19 hard drawn compact round conductors cabled around a neutral
conductor
Insulation: Abrasion, heat and moisture resistant cross linked polyethylene (XLP) insulation rated 90°C/-40°C
Neutral: Compact round ASCR neutral. For sizes 266.8kcmil and greater, ACSR neutral conductors shall be in concentric round stranding
Phase ID:

Cable Construction Phase 1 Phase 2 Phase 3
Duplex Black with print legend - -
Triplex Black with print legend Black with  red stripes -
Quadruplex Black with print legend Black with  red stripes Black with blue stripes
NS75/NS90 Quadruplex Unjacketed Overhead Neutral Supported Cable Parameter
PHASE CONDUCTORS ACSR COMPACT BARE NEUTRAL OVERALL
SIZE
(AWG OR kcmil)
NO. OF WIRES COND. O.D. MIN. INS. THKN.  NOM. INS. O.D. SIZE  NO. OF WIRES  RATED STRENGTH COND. O.D.  EFFECTIVE O.D.  APPROX. WEIGHT AMPACITY
(mm) (mm) (mm) (AWG OR kcmil) (A1/S1A) kN (mm) (mm) (kg/km)
6 7 4.29 1.04 6.63 6 6/1 5.18 5.03 15 224 85
4 7 5.41 1.04 7.75 4 6/1 8.14 6.35 18 335 110
2 7 6.81 1.04 9.14 2 6/1 12.4 8.11 21 507 150
1/0 7 8.53 1.37 11.6 1/0 6/1 18.9 10.1 27 803 200
2/0 7 9.65 1.37 12.6 2/0 6/1 23.5 11.5 30 991 230
3/0 7 10.7 1.37 13.8 3/0 6/1 29.6 12.8 33 1224 265
4/0 7 12.1 1.37 15.2 4/0 6/1 37.3 14.3 36 1519 305
266.8 19 13.6 1.83 17.7 266.8 26/7 50.1 16.3 42 1955 355
336.4 19 15.3 1.83 19.4 336.4 26/7 62.3 18.3 46 2421 410
397.5 19 16.7 1.83 20.8 397.5 26/7 71.6 19.9 50 2828 455
477 19 18.3 1.83 22.4 477 26/7 86 21.8 54 3359 510