Quadruplex Aluminum Service Drop Cable Application
Quadruplex AluminumService Drop Cable used to supply 3-phase power, usually from a polemounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-tophase or less and at conductor temperatures not to
exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors
Quadruplex Aluminum Service Drop Cable Standard
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts
Quadruplex Overhead Service Drop Cable Construction

Quadruplex Overhead Service Drop Cable Construction
Phase Conductor |
Strand or Compressed 1350-H19 Series Aluminum Conductor. |
Neutral(Messenger)Conductor |
Bare ACSR messenger. Optional constructions include a messenger of AAC or 6201 alloy. |
Insulation |
Black Cross Linked Polyethylene (XLP) Insulation. |
Quadruplex Overhead Service Drop Cable Technical Data
Rated voltage |
kV |
0.6/1 |
Test voltage |
Veff kV/Hz |
4/50 |
Laying temperature |
°C |
min. -5 |
Operating temperature |
°C |
-30 ~ +90 |
Conductor temperature |
°C |
max. +90 |
Short-circuit temperature |
°C/s |
max. +250 /5 |
Bending radius (min.) |
mm |
20 × Ø of cable |