4mm 2 Core Steel Wire Armoured SWA Cable

This 4mm² 2-core steel wire armoured (SWA) cable is designed for low voltage applications with a voltage rating of 0.6/1kV. It features durable steel wire armouring for enhanced mechanical protection, making it suitable for outdoor and underground installations. The cable provides reliable electrical performance and robust physical protection, ideal for industrial, commercial, and infrastructure power distribution where durability is essential.

  • slide

4mm 2 Core Steel Wire Armoured SWA Cable


4mm 2 Core Steel Wire Armoured SWA Cable Low Voltage 0.6/1kV

  • Rated Voltage 600/1000 Volts
  • Conductor Material Copper or Aluminum
  • Insulation Cross Linked Poly Ethylene (XLPE)
  • Armour Steel Wire Armoured
  • Oversheath PVC or LSZH


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

4mm 2 Core SWA Armoured Cable Application

These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. The lead sheath brings an enhanced resistance to aromatic hydrocarbons.

4mm 2 Core SWA Armoured Cable Standard

BS 5467 IEC 60502-1.

CONSTRUCTION :

2 Core Steel Wire Armoured SWA Cable Construction

2 Core Steel Wire Armoured SWA Cable Construction

Conductors: Plain circular, compacted or shaped stranded copper or aluminium conductor (Conductor shaped: RE=circular solid, CC=compacted circular stranded, SM=sector shaped stranded)

Insulation: XLPE (cross-linked polyethylene) rated at 90°C

Color identification

1 Core : Red or Black, 2 Cores : Red, Black, 3 Cores: Red, Yellow, Blue , 4 Cores: Red, Yellow, Blue, Black, 5 Cores: Red, Yellow, Blue, Black, Green

Above 5 Cores: Black Cores with White numerals

*The above identifying can be changed as user requirement

Assembly /Inner Sheath:Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers and the assembly is bedded with an extruded layer of PVC. In case of non-armoured cables, this layer may be omitted

Armour: Galvanized Steel Wires, single core cables shall be Aluminium wire armour, Aluminum/Steel Tapes applied helically over the bedding of multi-core cables as per IEC 60502.

Sheath:Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.

Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSZH, and CPE are available on request.

Fire Performance of Cable Sheaths

Cables can be supplied with special flame retardant PVC outer sheath to comply With the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, we can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards.

TECHNICAL DATA :
2 Core SWA Armoured Cable Technical Data

4mm 2 Core Steel Wire Armoured SWA Cable Technical Data
Voltage: 600/1000v

Operating temperature: Maximum 90°C, minimum bending 0°C

Maximum short-circuit temperature: 250°C(max. 5s)

Minimum bending raduis: x20 cable diameter (armoured)

2 Core SWA Armoured Cable Parameter
0.6/1kV-2 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Steel Wire diameter Sheath thickness Approximate outer diameter Approx.
weight
Max.D.C resistance of conductor(20℃) Current carrying capacity
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
2X2.5 0.7 0.8 1.8 14.8 364 7.41 23 32
2X4 0.7 0.8 1.8 15.7 425 4.61 30 41
2X6 0.7 1.25 1.8 17.6 646 3.08 39 53
2X10 0.7 1.25 1.8 20.1 802 1.83 53 70
2X16 0.7 1.25 1.8 22.3 1008 1.15 68 91
2X25 0.9 1.6 1.8 26.3 1470 0.727 91 116
2X35 0.9 1.6 1.8 27.6 1712 0.524 112 140
2X50 1 1.6 1.9 30.8 2123 0.387 137 168
2X70 1.1 2 2 35.4 2974 0.268 172 203
2X95 1.1 2 2.1 39.5 3737 0.193 214 249
2X120 1.2 2 2.3 42.9 4453 0.153 249 284
2X150 1.4 2.5 2.4 48 5744 0.124 284 315
2X185 1.6 2.5 2.6 52.7 6811 0.0991 326 357