240mm 4 Core Steel Wire Armoured SWA Cable

This is a 4-core, 240mm² steel wire armoured (SWA) cable designed for low-voltage power transmission rated at 0.6/1kV. It consists of four insulated copper conductors, each with a cross-sectional area of 240mm², protected by a steel wire armour that provides high mechanical strength, durability, and resistance to physical damage. This type of cable is ideal for heavy-duty applications such as industrial power distribution, underground wiring, and outdoor installations where robust mechanical protection and high current capacity are essential for safe and reliable operation.

  • slide

240mm 4 Core Steel Wire Armoured SWA Cable


240mm4 Core Steel Wire Armoured SWA Cable Low Voltage 0.6/1kV

  • Rated Voltage 600/1000 Volts
  • Conductor Material Copper or Aluminum
  • Insulation Cross Linked Poly Ethylene (XLPE)
  • Armour Steel Wire Armoured
  • Oversheath PVC or LSZH
  • Number of cores 4core


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

240mm 4 Core Steel Wire Armoured SWA Cable Application

240mm 4 Core Steel Wire Armoured SWA Cable made up of a black PVC sheath, XLPE insulation, copper conductors and steel wire armouring. This type of cable is designed for mains electricity in various applications, including laying underground, power networks, incoming mains to homes amongst a host of other uses externally and internally.

240mm 4 Core Steel Wire Armoured SWA Cable is suitable and often used for direct burial, with the steel wire armouring providing further protection from external damaged. The XLPE insulation is resistant to a number of different fluids, chemicals and has good heat stability, as well as being UV Resistant.

240mm 4 Core Steel Wire Armoured SWA Cable Standard

BS 5467, IEC/EN 60502-1, IEC/EN 60228 , Flame Retardant according to IEC/EN 60332-1-2

CONSTRUCTION :

240mm 4 Core Steel Wire Armoured SWA Cable Construction

4 Core Steel Wire Armoured SWA Cable Construction

4 Core Steel Wire Armoured SWA Cable Construction

Conductors: Plain circular, compacted or shaped stranded copper or aluminium conductor (Conductor shaped: RE=circular solid, CC=compacted circular stranded, SM=sector shaped stranded)

Insulation: XLPE (cross-linked polyethylene) rated at 90°C

Color identification

1 Core : Red or Black, 2 Cores : Red, Black, 3 Cores: Red, Yellow, Blue , 4 Cores: Red, Yellow, Blue, Black, 5 Cores: Red, Yellow, Blue, Black, Green

Above 5 Cores: Black Cores with White numerals

*The above identifying can be changed as user requirement

Assembly /Inner Sheath:Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers and the assembly is bedded with an extruded layer of PVC. In case of non-armoured cables, this layer may be omitted

Armour: Galvanized Steel Wires, single core cables shall be Aluminium wire armour, Aluminum/Steel Tapes applied helically over the bedding of multi-core cables as per IEC 60502.

Sheath:Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.

Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSZH, and CPE are available on request.

Fire Performance of Cable Sheaths

Cables can be supplied with special flame retardant PVC outer sheath to comply With the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, we can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards.

TECHNICAL DATA :

240mm 4 Core Steel Wire Armoured SWA Cable Technical Data
Voltage: 600/1000v

Operating temperature: Maximum 90°C, minimum bending 0°C

Maximum short-circuit temperature: 250°C(max. 5s)

Minimum bending raduis: x20 cable diameter (armoured)

PARAMETER :

240mm 4 Core Steel Wire Armoured SWA Cable Parameter

Type Specification Outer diameter Nominal
thickness
of insulation
Diameter of
steel wire
Nominal
sheath
thickness
Approx.
Outer
diameter
of cable
Approx. Weight
of cable
Ampacity of cable
 Air Soil
CU AL Cu Al Cu Al
XLPE/SWA mm2 mm mm mm mm mm kg/km kg/km A A A A
4×4 RE 2.24 0.7 1.25 1.8 19.1 770 670 37 28 46 35
4×6 RE 2.76 0.7 1.25 1.8 20.3 916 772 47 37 56 46
4×10 CC 3.8 0.7 1.6 1.8 22.3 1148 895 64 47 76 56
4×16 CC 4.8 0.7 1.6 1.8 24.5 1472 1070 84 64 98 76
4×25 CC 6.0 0.9 1.6 1.8 27.5 1942 1317 115 84 126 98
4×35 CC 7.0 0.9 1.6 1.8 29.5 2386 1521 141 115 152 126
4×50 SM 8.0 1.0 2.0 1.9 32.9 3209 2036 172 141 181 152
4×70 SM 9.5 1.1 2.0 2.1 36.7 4197 2502 218 172 222 181
4×95 SM 11.0 1.1 2.0 2.3 40.5 5362 3016 269 218 267 222
4×120 SM 12.4 1.2 2.5 2.4 45.3 6908 3940 313 269 305 267
4×150 SM 13.8 1.4 2.5 2.6 50.0 8327 4683 359 313 344 305
4×185 SM 15.4 1.6 2.5 2.7 54.2 10044 5466 405 359 383 344
4×240 SM 17.5 1.7 2.5 2.9 60.4 12672 6666 451 405 442 383
4×300 SM 19.6 1.8 2.5 3.1 65.7 15302 7795 497 451 461 422