XLPE Insulated 120mm2 2 Cores Copper Cable 2x120mm2

This is a 120mm² cross-sectional area, XLPE insulated, PVC sheathed, unarmoured copper cable with 2 cores, rated at 0.6/1kV. It is designed for high-current power distribution applications, offering excellent electrical performance, thermal stability, and environmental resistance. Suitable for large-scale industrial, commercial, or infrastructure projects where robust and reliable power transmission is required.

  • slide

XLPE Insulated 120mm2 2 Cores Copper Cable 2x120mm2


XLPE Insulated, PVC Sheathed Unarmoured 120mm2 2 Cores Copper Cable, 0.6/1kV

  • Number of cores 2
  • Cross section area 120mm2
  • Conductor Copper
  • Rated Voltage 600/1000 Volts
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

XLPE 120mm2 2 Cores Copper Cable Application

XLPE insulated 2-core power cables are normally used in power transmission and distribution systems. The 2-core XLPE cable is referred to as IEC60502 CU/XLPE/PVC 0.6/1KV.

These cables are used for outdoor and indoor installations in damp and wet applications. They are normally used for power distribution in urban networks, industrial plants and energy distribution. For mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage. Suitable where space is at a premium.

XLPE 120mm2 2 Cores Copper Cable Standard

IEC 60228 Conductors
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) - Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV)

CONSTRUCTION :

XLPE 120mm2 2 Cores Copper Cable Construction
1. Conductor: Plain annealed copper, Class 1: solid conductor, or Class 2: stranded conductor
2. Insulation: Cross-linked polyethylene XLPE
3. Filler: Non-hygroscopic material
4. Binder tape: Non-hygroscopic material
5. Outer sheath: Polyvinyl chloride PVC

XLPE 2 Cores Copper Cable Construction

XLPE 2 Cores Copper Cable Construction

PARAMETER :

XLPE 120mm2 2 Cores Copper Cable Parameter

Cable Type: CU/XLPE/PVC
Operating voltage, U0 / U (V): 600/1000
Number of cores: 2
Nominal Area (mm2): 120
Conductor Stranding: 24
Insulation Thickness (mm): 1.2
Sheath Thickness (mm): 2.0
Cable Overall Diameter (O.D.) (mm): 29.4
Cable Weight Per 1000 Meters (kg): 2450
Resistance DC 20°C Per 1000 Meters (Ω): 0.153
Allowable Ampacity in Air (Amps): 355
Allowable Ampacity  in Ground (Amps): 405
Test Voltage:
3.5kV for 5 minutes
Operating temperature (°C) : -15 to +90

Final short circuit temperature (°C):

250