XLPE Insulated 1.5mm2 3 Cores Copper Cable 3×1.5mm2

This is a 3-core copper cable with a cross-sectional area of 1.5mm² per core, featuring XLPE insulation and PVC sheathing. Rated at 0.6/1kV, it is suitable for low to moderate power distribution applications. The XLPE insulation provides excellent thermal resistance, electrical performance, and durability, while the PVC sheath offers environmental protection. Being unarmoured, it is ideal for indoor use or protected outdoor environments where mechanical protection from external forces is not required.

  • slide

XLPE Insulated 1.5mm2 3 Cores Copper Cable 3x1.5mm2


XLPE Insulated, PVC Sheathed Unarmoured 1.5mm2 3 Cores Copper Cable, 0.6/1kV

  • Number of cores 3
  • Cross section area 1.5mm2
  • Conductor Copper
  • Rated Voltage 600/1000 Volts
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

XLPE 1.5mm2 3 Cores Copper Cable Application

XLPE insulated 3-core power cables are normally used in power transmission and distribution systems. The 3-core XLPE cable is referred to as IEC60502 CU/XLPE/PVC 0.6/1KV.

These cables are used for outdoor and indoor installations in damp and wet applications. They are normally used for power distribution in urban networks, industrial plants and energy distribution. For mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage. Suitable where space is at a premium.

XLPE 1.5mm2 3 Cores Copper Cable Standard

IEC 60228 Conductors
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) - Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV)

CONSTRUCTION :

XLPE 1.5mm2 3 Cores Copper Cable Construction
1. Conductor: Plain annealed copper, Class 1: solid conductor, or Class 2: stranded conductor
2. Insulation: Cross-linked polyethylene XLPE
3. Filler: Non-hygroscopic material
4. Binder tape: Non-hygroscopic material
5. Outer sheath: Polyvinyl chloride PVC

XLPE 3 Core Copper Cable Construction

XLPE 3 Core Copper Cable Construction

PARAMETER :

XLPE 1.5mm2 3 Cores Copper Cable Parameter

Cable Type: CU/XLPE/PVC
Operating voltage, U0 / U (V): 600/1000
Number of cores: 3
Nominal Area (mm2): 1.5
Conductor Stranding: 1 or 7
Insulation Thickness (mm): 0.7
Sheath Thickness (mm): 1.8
Cable Overall Diameter (O.D.) (mm): 11.8
Cable Weight Per 1000 Meters (kg): 135
Resistance DC 20°C Per 1000 Meters (Ω): 12.1
Allowable Ampacity in Air (Amps): 21
Allowable Ampacity  in Ground (Amps): 30
Test Voltage:
3.5kV for 5 minutes
Operating temperature (°C) : -15 to +90
Final short circuit temperature (°C):
250