The XLPE insulated 3-core 400mm² copper cable is a high-capacity power cable designed for reliable transmission and distribution of electricity in both industrial and commercial applications. Constructed with cross-linked polyethylene (XLPE) insulation and copper conductors, this cable offers excellent electrical performance, mechanical strength, and thermal resistance. It complies with international standards and is widely used in medium- to low-voltage installations.
Application
This 3-core XLPE insulated copper cable, rated 0.6/1kV (IEC 60502 CU/XLPE/PVC), is suitable for indoor and outdoor installations, including damp and wet environments. Common applications include:
-
Power distribution in urban networks and industrial facilities
-
Mains and submains for buildings and substations
-
Installation in conduits, ducts, direct burial, or cable trays
-
Areas where space is limited and flexibility is essential
-
Suitable for installations not subject to severe mechanical stress
Maximum operating temperature:
-
90°C continuous (XLPE insulation)
-
250°C short circuit (5s max)
Standards
-
IEC 60228 – Conductors of insulated cables
-
IEC 60502-1 – Power cables with extruded insulation for rated voltages of 1kV (Um = 1.2kV) and 3kV (Um = 3.6kV)
Construction
| Component | Description |
|---|---|
| Conductor | Plain annealed copper (Class 2 stranded or Class 1 solid) |
| Insulation | XLPE (Cross-linked polyethylene) |
| Filler | Non-hygroscopic material |
| Binder Tape | Non-hygroscopic wrapping |
| Outer Sheath | PVC (Polyvinyl chloride) – black or as specified |

XLPE 3 Core Copper Cable Construction
PARAMETER :
XLPE 400mm2 3 Cores Copper Cable Parameter
| Cable Type: | CU/XLPE/PVC |
| Operating voltage, U0 / U (V): | 600/1000 |
| Number of cores: | 3 |
| Nominal Area (mm2): | 400 |
| Conductor Stranding: | 60 |
| Insulation Thickness (mm): | 2.0 |
| Sheath Thickness (mm): | 3.0 |
| Cable Overall Diameter (O.D.) (mm): | 62.4 |
| Cable Weight Per 1000 Meters (kg): | 10000 |
| Resistance DC 20°C Per 1000 Meters (Ω): | 0.0470 |
| Allowable Ampacity in Air (Amps): | 640 |
| Allowable Ampacity in Ground (Amps): | 640 |
| Test Voltage: | 3.5kV for 5 minutes |
| Operating temperature (°C) : | -15 to +90 |
| Final short circuit temperature (°C): | 250 |