PVC Insulated Wire (60227 KS IEC 01), 450/750V IV

The 450/750V IV PVC insulated wire is designed for internal wiring in buildings and electric equipment. It is commonly used for fixed wiring in lighting systems, control panels, switchboards, and electrical appliances operating at voltages up to 750V. Suitable for indoor installations where flexibility and easy handling are required.

  • Pvc Insulated Wire 60227 Ks Iec 01

PVC Insulated Wire (60227 KS IEC 01), 450/750V IV


PVC Insulated Wire IV

  • Conductor Material Copper Conductor
  • Insulation PVC
  • Voltage 450/750V
  • Number of cores Single Core
  • Package 100 Meters One Roll with Export Wooden Case & Pallet


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

The 450/750V IV PVC insulated wire is designed for internal wiring in buildings and electric equipment. It is commonly used for fixed wiring in lighting systems, control panels, switchboards, and electrical appliances operating at voltages up to 750V. Suitable for indoor installations where flexibility and easy handling are required.

Standards:
Manufactured in accordance with KS C IEC 60227-3 (equivalent to 60227 IEC 01) standard for PVC insulated cables for rated voltages up to and including 450/750V.

CONSTRUCTION :

PVC Insulated Wires IV Construction

PVC Insulated Wires IV Construction

PVC Insulated Wires IV Construction

– Conductor : Annealed copper wire for electrical use (solid wire, circular copper wire, circular compressed copper wire)
– Insulator : Polyvinyl Chloride (PVC/C)
– Insulator coloring : Black, white, red, green, yellow, blue
– Highest temperature : 70℃

TECHNICAL :

PVC Insulated Wires IV Technical Data

Nominal voltage Uo/U [V]450 / 750 volt
Test voltage [V]AC2500
Temperature rangein motion +5°C till +70°C
Operating temperatureshort circuit°C160
Short circuit timemax.[sec]5
Bending radiusmin.x diameter4
Flammabilitystandard 60227 KS IEC 01
PVC Insulated Wires IV Parameter
ConductorNominal
Insulation
Thickness
Overall
Diameter
Max.
Conductor
Resistance
at 20℃
Min.
Insulation
Resistance
at 70℃
Test
Voltage
Approx.
Weight
Standard
Length
Nominal
Sectional
Area
Conductor
Class
mm2mmmmΩ/kmMΩ/kmV/5minkg/kmm
1.510.73.212.10.011250020300
1.520.73.312.10.01250025300
2.510.83.97.410.01250035300
2.520.84.07.410.009250035300
410.84.44.610.0085250050300
420.84.64.610.0077250055300
610.85.03.080.007250070300
620.85.23.080.0065250075300
1011.06.41.830.0072500115300
1021.06.71.830.00652500120300
1621.07.81.150.0052500170300
2521.29.70.7270.0052500270300
3521.210.90.5240.00432500370300
5021.412.80.3870.00432500510300
7021.414.60.2680.00352500685300
9521.617.10.1930.00352500935300
12021.618.80.1530.003225001,170300
15021.820.90.1240.003225001,450300
18522.023.30.09910.003225001,820300
24022.026.60.07540.003225002,305200
30022.429.60.06010.003025002,925200
40022.633.20.04700.002825003,820200
Need Help?