PVC Insulated Flexible Wire (60227 KS IEC 02) 450/750V KIV

PVC Insulated Flexible Wire (60227 KS IEC 02), rated at 450/750V, is a highly flexible electrical wire designed for versatile wiring applications. Made with copper conductors and insulated with high-quality PVC, this wire offers excellent flexibility, ease of installation, and durability. Ideal for use in domestic, commercial, and industrial settings where flexible wiring is required, it ensures reliable electrical performance and safety. Its compliance with international standards guarantees suitability for a wide range of electrical systems, providing safe and efficient power transmission.

  • Pvc Insulated Flexible Wire

PVC Insulated Flexible Wire (60227 KS IEC 02) 450/750V KIV


PVC Flexible Wire KIV

  • Conductor Material Copper Conductor
  • Insulation PVC
  • Voltage 450/450V
  • Number of cores Single Core
  • Package 100 Meters One Roll with Export Wooden Case & Pallet


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

PVC Insulated Wire HIV Application

This wire is suitable for the inner-wiring of a structure or electrical equipments under AC 300/500V and insulated by the PVC which has property of heat-resistant

PVC Insulated Wire HIV Standards:

60227 KS IEC 07

CONSTRUCTION :

PVC Insulated Flexible Wire (60227 KS IEC 02) 450/750V KIV Construction
– Conductor : Grade 5 conductor (stranded conductor, composite conductor)
– Insulator : Polyvinyl Chloride (PVC/C)
– Color of insulator : Black, white, red, green, yellow, blue
– Highest temperature : 70 ℃

TECHNICAL :

PVC Insulated Flexible Wire (60227 KS IEC 02) 450/750V KIV Technical Data

Nominal voltage Uo/U   [V] 450 / 750 volt
Test voltage   [V]AC 2500
Temperature range in motion   +5°C till +70°C
Operating temperature short circuit °C 160
Short circuit time max. [sec] 5
Bending radius min. x diameter 4
Flammability standard   60227 KS IEC 02
PVC Insulated Wires IV Parameter
Conductor Nominal
Insulation
Thickness
Overall
Diameter
Max.
Conductor
Resistance
at 20℃
Min.
Insulation
Resistance
at 70℃
Test
Voltage
Approx.
Weight
Nominal
Sectional
Area
Number &
Diameter
of Wire
Outer
Diameter
Lower
Limit
Upper
Limit
mm2 No./mm mm mm mm Ω/km MΩ/km V/5min kg/km
1.5 28/0.26 1.6 0.7 2.8 3.4 13.30 0.010 2500 21
2.5 47/0.26 2.1 0.8 3.4 4.1 7.98 0.009 2500 33
4 53/0.31 2.6 0.8 3.9 4.8 4.95 0.007 2500 48
6 80/0.31 3.2 0.8 4.4 5.3 3.30 0.006 2500 68
10 76/0.41 4.2 1.0 5.7 6.8 1.91 0.0056 2500 112
16 121/0.41 5.2 1.0 6.7 8.1 1.21 0.0046 2500 170