H05V-U H07V-U PVC Insulated Single Core Wire

H05V-U and H07V-U are types of PVC-insulated single-core wires commonly used in electrical wiring. H05V-U is rated for up to 300/500V and is suitable for internal wiring of appliances, control panels, and lighting, offering flexibility and safety for dry or damp environments. H07V-U, with a voltage rating of up to 450/750V, is used in fixed wiring for power distribution and control circuits within buildings, accommodating higher voltage demands. Both wires are made of copper conductors, with durable PVC insulation that is flame retardant and resistant to mechanical stress, making them reliable choices for indoor electrical installations.

  • H05v U H07v U Pvc Insulated Single Core Wire

H05V-U H07V-U PVC Insulated Single Core Wire


Electric Wire and Cable H05V-U H07-U

  • Conductor Material Copper Conductor
  • Insulation PVC
  • Voltage 450/750V
  • Number of cores Single Core
  • Package 100 Meters One Roll with Export Wooden Case & Pallet


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

H05V-U H07V-U Wire Application

For protected fixed installations inside appliances and in or on lighting fittings. Further for installations in pipes on and under plaster, however, only for signal circuit and control circuit. The cable is not suitable for direct laying under plaster, however, only for signal circuit and control circuit.

H05V-U H07V-U Wire Standards:

DIN VDE 0281-3 DIN EN 60228

CONSTRUCTION :

H05V-U H07V-U Wire Construction

H05V-U H07V-U Wire Construction

H05V-U H07V-U Wire Construction

Conductor : solid bare copper
Insulation: PVC (Polyvinyl chloride)

TECHNICAL :

H05V-U H07V-U WireTechnical Data

Nominal voltage Uo/U   [V] 300 / 500 volt
Test voltage   [V]AC 2000
Temperature range in motion   +5°C till +70°C
Operating temperature short circuit °C 160
Short circuit time max. [sec] 5
Bending radius min. x diameter 4
Flammability standard   EN 60332-1-2
H05V-U H07V-U Parameter
No. of Cores x Nominal Cross Sectional Area Nominal Thickness of Insulation Nominal Overall Diameter Nominal Copper Weight Nominal Weight
# x mm^2 mm mm kg/km kg/km
H05V-U
1 x 0.5 0.6  2.1 4.8 9
1 x 0.75 0.6 2.2 7.2 11
1 x 1 0.6 2.4 9.6 14
H07V-U
1 x 1.5 0.7  2.9 14.4 21
1 x 2.5 0.8 3.5 24.0 33
1 x 4 0.8 3.9 38.0 49
1 x 6 0.8 4.5 58.0 69
1 x 10 1.0 5.7 96.0 115
Need Help?