3-Layer 35kV AAAC Tree Wire Spacer Cable

This cable is a specialized covered conductor for medium-voltage overhead power distribution. The 3-Layer 35kV AAAC Tree Wire Spacer Cable has a multi-layered protective covering that prevents direct shorts and flashovers caused by external objects like tree limbs. This makes it an excellent choice for areas with limited space or where power lines pass through wooded regions.

  • 3 Layer 35kv Aaac Tree Wire Spacer Cable

3-Layer 35kV AAAC Tree Wire Spacer Cable


3-Layer 35kV AAAC Tree Wire Spacer Cable

  • Conductor 6201-81 aluminum alloy (AAAC)
  • Insulation Cross-linked polyethylene(XLPE)
  • Sheath High-density track-resistant Polyethylene(HDPE)
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

This cable is a specialized covered conductor for medium-voltage overhead power distribution. The 3-Layer 35kV AAAC Tree Wire Spacer Cable has a multi-layered protective covering that prevents direct shorts and flashovers caused by external objects like tree limbs. This makes it an excellent choice for areas with limited space or where power lines pass through wooded regions.


Key Specifications & Construction

  • Voltage: 35 kV phase-to-phase.
  • Conductor: Concentrically stranded All Aluminum Alloy Conductor (AAAC), made from 6201-T81 aluminum alloy. This provides high strength and excellent conductivity.
  • Layers: The '3-layer' design typically includes a semi-conducting layer, the primary insulation, and a final protective outer layer.
  • Insulation: The primary insulating layer is cross-linked polyethylene (XLPE).
  • Sheath: The outermost layer is a high-density track-resistant polyethylene (HDPE).
  • Standards: The cable complies with key industry standards, including ICEA S-121-733, ASTM B231, ASTM B399, and ASTM B232.

Technical Data

  • Normal Operating Temperature: 90°C.
  • Emergency Overload Temperature: 130°C.
  • Short Circuit Temperature: 250°C.
  • AC Testing Voltage: The cable is tested at a voltage suitable for a 35 kV rating.

Parameter Table

Size (kcmil) Stranding Conductor Diameter (mils) Covering Thickness (mils) Cable O.D. (mils) Rated Strength (lbs) Weight per 1000 ft (lbs)
48.6 7 250 15/175/125 880 1584 278
77.4 7 316 15/175/125 946 2520 333
123.3 7 398 15/175/125 1028 4014 411
155.4 7 447 15/175/125 1077 4851 462
195.7 7 502 15/175/125 1132 6111 523
246.9 7 563 15/175/125 1193 7704 598
266.8 19 642 15/175/125 1272 9900 689
336.4 19 720 15/175/125 1351 11970 799
397.5 19 783 15/175/125 1412 14040 892
477 19 858 20/175/125 1498 16920 1024
556.5 19 927 20/175/125 1567 19710 1141
636 37 990 20/175/125 - - -
795 37 1108 20/175/125 - - -