Triplex URD Cable Aluminum Secondary Underground Direct Burial Cable 600V

The 600V Triplex URD (Underground Residential Distribution) cable is designed for underground secondary distribution. It consists of three insulated conductors twisted together, typically two phase conductors and one neutral conductor. This cable is suitable for direct burial in the earth or installation in ducts in both wet or dry locations, with a maximum operating temperature of 90 ∘ C.

  • Triplex Urd Cable Aluminum Secondary Underground Direct Burial Cable 600v

Triplex URD Cable Aluminum Secondary Underground Direct Burial Cable 600V


Triplex URD Cable Aluminum Secondary Underground Direct Burial Cable 600V

  • Conductor 1350-H19 series or AA-8000 aluminum alloy compressed aluminum conductors
  • Insulation Black resistant cross-linked polyethylene (XLP) insulation
  • Voltage 600V


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

The 600V Triplex URD (Underground Residential Distribution) cable is designed for underground secondary distribution. It consists of three insulated conductors twisted together, typically two phase conductors and one neutral conductor. This cable is suitable for direct burial in the earth or installation in ducts in both wet or dry locations, with a maximum operating temperature of C.


Key Specifications & Construction

  • Voltage: 600V.
  • Conductor: Both phase and neutral conductors are made from a Class B compressed concentric lay stranded aluminum alloy (1350-H19 or AA-8000 series).
  • Insulation: The conductors are insulated with black thermoset XLPE (cross-linked polyethylene). The neutral conductor is distinguished by a yellow stripe or a full yellow jacket.
  • Configuration: Three insulated conductors (two phase and one neutral) are twisted together.
  • Standards: The cable complies with ICEA S-105-692 and UL 854 (as USE-2) and is RUS accepted.
  • Features: The cable is resistant to heat, ozone, oil, and chemicals. It is also tear and abrasion-resistant, and suitable for direct burial.

Technical Data

  • Normal Operating Temperature: C.
  • Application: Suitable for direct burial or installation in ducts in both wet and dry locations.

Parameter Table

Code NamePhase Conductor (AWG)Neutral (AWG)Diameter (mils)Weight/kft (lbs)Ampacity (Direct Burial)Ampacity (In Ducts)
Erskine666441369570
Vassar4474519412590
Stephens24870260165120
Ramapo22870290165120
Brenau1/021106409215160
Bergen1/01/01106476215160
Converse2/011199490245180
Hunter2/02/01199540245180
Hollins3/01/01302586280205
Sweetbriar4/02/01421740315240
Monmouth4/04/01421847315240
Pratt250 kcmil3/01581857345265
Wesleyan350 kcmil4/017951135415320
Rider500 kcmil350 kcmil21171248495395
Fairfield750 kcmil500 kcmil28602304615525