Triplex URD Cable Aluminum Secondary Underground Direct Burial Cable 600V

The 600V Triplex URD (Underground Residential Distribution) cable is designed for underground secondary distribution. It consists of three insulated conductors twisted together, typically two phase conductors and one neutral conductor. This cable is suitable for direct burial in the earth or installation in ducts in both wet or dry locations, with a maximum operating temperature of 90 ∘ C.

  • Triplex Urd Cable Aluminum Secondary Underground Direct Burial Cable 600v

Triplex URD Cable Aluminum Secondary Underground Direct Burial Cable 600V


Triplex URD Cable Aluminum Secondary Underground Direct Burial Cable 600V

  • Conductor 1350-H19 series or AA-8000 aluminum alloy compressed aluminum conductors
  • Insulation Black resistant cross-linked polyethylene (XLP) insulation
  • Voltage 600V


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

The 600V Triplex URD (Underground Residential Distribution) cable is designed for underground secondary distribution. It consists of three insulated conductors twisted together, typically two phase conductors and one neutral conductor. This cable is suitable for direct burial in the earth or installation in ducts in both wet or dry locations, with a maximum operating temperature of C.


Key Specifications & Construction

  • Voltage: 600V.
  • Conductor: Both phase and neutral conductors are made from a Class B compressed concentric lay stranded aluminum alloy (1350-H19 or AA-8000 series).
  • Insulation: The conductors are insulated with black thermoset XLPE (cross-linked polyethylene). The neutral conductor is distinguished by a yellow stripe or a full yellow jacket.
  • Configuration: Three insulated conductors (two phase and one neutral) are twisted together.
  • Standards: The cable complies with ICEA S-105-692 and UL 854 (as USE-2) and is RUS accepted.
  • Features: The cable is resistant to heat, ozone, oil, and chemicals. It is also tear and abrasion-resistant, and suitable for direct burial.

Technical Data

  • Normal Operating Temperature: C.
  • Application: Suitable for direct burial or installation in ducts in both wet and dry locations.

Parameter Table

Code Name Phase Conductor (AWG) Neutral (AWG) Diameter (mils) Weight/kft (lbs) Ampacity (Direct Burial) Ampacity (In Ducts)
Erskine 6 6 644 136 95 70
Vassar 4 4 745 194 125 90
Stephens 2 4 870 260 165 120
Ramapo 2 2 870 290 165 120
Brenau 1/0 2 1106 409 215 160
Bergen 1/0 1/0 1106 476 215 160
Converse 2/0 1 1199 490 245 180
Hunter 2/0 2/0 1199 540 245 180
Hollins 3/0 1/0 1302 586 280 205
Sweetbriar 4/0 2/0 1421 740 315 240
Monmouth 4/0 4/0 1421 847 315 240
Pratt 250 kcmil 3/0 1581 857 345 265
Wesleyan 350 kcmil 4/0 1795 1135 415 320
Rider 500 kcmil 350 kcmil 2117 1248 495 395
Fairfield 750 kcmil 500 kcmil 2860 2304 615 525
Need Help?