LXAV Cable Construction
Application
LXAV cables are designed for low-voltage power distribution in environments where mechanical protection is essential. These cables are suitable for outdoor fixed installations, especially in areas exposed to:
-
Mechanical impact or pressure
-
Rodent threats
-
Direct burial or duct installation
-
Industrial zones and utility networks
The armored structure ensures excellent durability and protection during installation and operation.
Standards
-
IEC 60502-1 – Power cables with extruded insulation up to 1kV
-
IEC 60332-1 – Flame propagation test
-
IEC 60228 – Conductors of insulated cables
-
EN 50575 – CPR Reaction to fire performance (Eca classification)
Construction
| Component | Description |
|---|---|
| Conductor | Stranded copper conductor, Class 2 (circular or sector-shaped), per IEC 60228 |
| Insulation | XLPE (cross-linked polyethylene), color-coded to HD 308.S2 |
| Armour Bedding | Black extruded PVC inner bedding/separation sheath |
| Armour | Double steel tape (for multicore) or aluminum tape (for single-core) |
| Outer Sheath | Flexible black PVC outer sheath, UV and weather resistant |
Core Identification (HD 308.S2)
-
1 core: Natural
-
2 cores: Blue + Brown
-
3 cores: Brown + Black + Grey
-
3G: Blue + Brown + Green/Yellow
-
3+1: Brown + Black + Grey + Blue (reduced neutral)
-
4G: Brown + Black + Grey + Green/Yellow
-
4 cores: Brown + Black + Grey + Blue
-
5G: Brown + Black + Grey + Blue + Green/Yellow
-
6+ cores: Black numbered + Green/Yellow
Technical Characteristics
| Property | Value |
|---|---|
| Voltage Rating (Uo/U) | 0.6/1kV |
| Test Voltage | 3.5kV (AC, 5 minutes) |
| Max Operating Temp | +90°C |
| Short-Circuit Temp (5s) | +250°C |
| Min Operating Temp (Fixed) | -40°C |
| Fire Performance | Flame-retardant to IEC 60332-1 |
| Halogen Emission | Low halogen, Cl < 15% |
| CPR Classification | Eca (EN 50575) |
Typical Cable Sizes and Weight (Excerpt)
| Configuration | Insul. Thick. (mm) | Sheath (mm) | OD (mm) | Weight (kg/km) |
|---|---|---|---|---|
| 2x10 mm² | 0.7 | 1.4 | 18.5 | 420 |
| 3x25 mm² | 0.9 | 1.6 | 26 | 830 |
| 3x70 mm² | 1.1 | 2.0 | 37.5 | 1710 |
| 3x150 mm² | 1.4 | 2.4 | 53 | 3770 |
| 4x16 mm² | 0.7 | 1.6 | 23.5 | 700 |
| 4x50 mm² | 1.0 | 1.9 | 35.5 | 1550 |
| 4x120 mm² | 1.2 | 2.4 | 53 | 3780 |
| 5x10 mm² | 0.7 | 1.6 | 22.5 | 640 |
Full specification table available upon request.
Why Choose LXAV Cable?
-
Reliable for outdoor and underground use
-
Strong mechanical protection with steel/aluminum armor
-
Resistant to rodents, impact, and moisture
-
Flame retardant and CPR compliant
-
Available in a wide range of cross-sections and core configurations