6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to IEC 60502

This is a medium-voltage (MV) Aerial Bundled Cable (ABC) designed for overhead power distribution. Unlike low-voltage ABC cables, this screened version includes multiple protective layers for use at higher voltages. It meets the IEC 60502 standard.

  • Screened Mv Abc Cable–aerial Bundled Cables To Iec 60502

6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to IEC 60502


6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to IEC 60502

  • Conductor Compact stranded hard drawn Aluminium Conductor ( Class2)
  • Conductor Screen Extruded semi-conductive layer
  • Insulation Cross-linked polyethylene (Natural)
  • Insulation Screen Extruded semi-conductive layer
  • Metallic Screen Copper wire screen or copper tape screen
  • Sheath HDPE


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

This is a medium-voltage (MV) Aerial Bundled Cable (ABC) designed for overhead power distribution. Unlike low-voltage ABC cables, this screened version includes multiple protective layers for use at higher voltages. It meets the IEC 60502 standard.

Strandard

IEC 60502

Construction

Phase Conductor Circular Compacted Stranded H68 Aluminium ( Class 2)
Conductor Screen Extruded Semi-conductive Layer.
Insulation XLPE.
Insulation Screen Extruded Semi-conductive Layer.
Metallic Screen Copper wire screen or copper tape screen
Separator Semi-conductive swellable tape.
Outer Sheath HDPE.
Support Conductor Galvanized steel wires.
Assembly XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay

Screened MV ABC Cable Construction

Screened MV ABC Cable Construction

Technical Data

Temperature :
- Normal operation 90°C.

- Emergency over load conditions 130°C.

- Short circuit conditions 250°C.

6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to IEC 60502 Parameter

NO.Cores X
Nominal Cross Section
Phase Conductor Messenger Suspension Unit Contiuous Current Rating
at 300C Ambient Temp
Stranding Nominal Sectional Area Stranding Nominal Sectional Area Breaking Load
No.×mm² No.×mm mm2 No.×mm mm2 KN A
3X50 + 1X25 19/1.78 50 7/3.0 50 60 116
3X70 + 1X50 19/2.14 70 7/3.15 50 62 210
3X95+ 1X50 19/2.52 95 7/3.0 50 60 173
3X185+1X120 37/2.52 185 7/4.67 120 150 259
3X150 +1X50 37/2.25 150 7/3.15 50 62 365
3X240 +1X50 61/2.25 240 7/3.15 50 62 500
Need Help?