6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to AS/NZS 3599.1 (AL/XLPE /CWS/HDPE)

This is a medium-voltage (MV) Aerial Bundled Cable (ABC) designed for overhead power distribution, built to the AS/NZS 3599.1 standard. The cable features a screened design for higher voltage applications, with three insulated cores bundled around a galvanized steel support wire. The construction is denoted by its materials: AL (aluminum conductor), XLPE (insulation), CWS (copper wire screen), and HDPE (sheath).

  • Screened Mv Abc Cable–aerial Bundled Cables

6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to AS/NZS 3599.1 (AL/XLPE /CWS/HDPE)


6.35/11kV Screened MV ABC Cable–Aerial Bundled Cables to AS/NZS 3599.1 (AL/XLPE /CWS/HDPE)

  • Conductor Compact stranded hard drawn Aluminium Conductor ( Class2)
  • Conductor Screen Extruded semi-conductive layer
  • Insulation Cross-linked polyethylene (Natural)
  • Insulation Screen Extruded semi-conductive layer
  • Metallic Screen Copper wire screen
  • Sheath HDPE


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

This is a medium-voltage (MV) Aerial Bundled Cable (ABC) designed for overhead power distribution, built to the AS/NZS 3599.1 standard. The cable features a screened design for higher voltage applications, with three insulated cores bundled around a galvanized steel support wire. The construction is denoted by its materials: AL (aluminum conductor), XLPE (insulation), CWS (copper wire screen), and HDPE (sheath).

Screened MV ABC Cable Construction

Key Specifications & Construction

  • Voltage: 6.35/11kV
  • Conductor: Compacted stranded hard-drawn aluminum (Class 2).
  • Conductor Screen: An extruded semi-conductive layer.
  • Insulation: Natural cross-linked polyethylene (XLPE).
  • Insulation Screen: An extruded semi-conductive layer.
  • Metallic Screen: Copper wire screen.
  • Sheath: High-density polyethylene (HDPE).
  • Support Conductor: Galvanized steel wires.
  • Assembly: Three XLPE-insulated and screened cores are bundled in a right-hand lay around the galvanized steel support conductor.

Applications and Technical Data

This cable is used for medium-voltage overhead distribution in applications like street lighting, outdoor lighting, and temporary construction services. It is suitable for a maximum conductor temperature of C.

  • Normal Operating Temperature: C
  • Emergency Overload Temperature: C
  • Short Circuit Temperature: C

MV ABC Aerial Bundled Cables to (AL/XLPE /CWS/HDPE) Parameter

Number of Cores x Nominal Cross Section Nominal Conductor Diameter Nominal Insulation Thickness Nominal Insulation Screen Thickness Copper Wire Screen Stranding Nominal Sheath Thickness Galvanized Steel Wire Stranding Nominal Overall Diameter Weight Continuous current rating, A
Still air 1m/s wind 2m/s wind
mm^2 mm mm mm No/mm mm No/mm mm kg/km A A A
Light duty screen
3x35 6.9 3.4 0.8 25/0.85 1.8 7/2.00 54.1 1820 99 140 165
3x35 6.9 3.4 0.8 25/0.85 1.8 19/2.00 58.1 2130 100 145 165
3x50 8.1 3.4 0.8 25/0.85 1.8 19/2.00 60.4 2300 120 170 200
3x70 9.7 3.4 0.8 25/0.85 1.8 19/2.00 63.6 2570 150 215 250
3x95 11.4 3.4 0.8 25/0.85 1.8 19/2.00 67 2900 180 260 305
3x120 12.8 3.4 0.8 25/0.85 1.8 19/2.00 69.8 3190 205 300 355
3x150 14.2 3.4 0.8 25/0.85 1.9 19/2.00 73 3530 235 340 400
3x185 15.7 3.4 0.8 25/0.85 1.9 19/2.00 76 3890 265 390 460
Heavy duty screen
3x35 6.9 3.4 0.8 40/0.85 1.8 7/2.00 54.1 2050 99 140 165
3x35 6.9 3.4 0.8 40/0.85 1.8 19/2.00 58.1 2360 100 145 165
3x50 8.1 3.4 0.8 23/1.35 1.8 19/2.00 62.4 2820 120 175 200
3x70 9.7 3.4 0.8 32/1.35 1.8 19/2.00 65.6 3440 150 215 250
3x95 11.4 3.4 0.8 39/1.35 1.8 19/2.00 69 4030 180 260 305
3x120 12.8 3.4 0.8 39/1.35 1.8 19/2.00 71.8 4320 205 300 355
3x150 14.2 3.4 0.8 39/1.35 1.9 19/2.00 75 4670 230 340 400
3x185 15.7 3.4 0.8 39/1.35 1.9 19/2.00 78 5020 265 390 460
Need Help?