2-Layer 15kV AAAC Tree Wire Spacer Cable

This cable is a specialized covered conductor for primary and secondary overhead distribution. It's designed for situations where space is limited, such as in congested areas or corridors. The cable's covering provides protection against direct shorts and flashovers with other objects, although it is not a fully insulated cable. The term "2-Layer" refers to the distinct layers of insulation and sheath.

  • 2 Layer 15kv Aaac Tree Wire Spacer Cable

2-Layer 15kV AAAC Tree Wire Spacer Cable


2-Layer 15kV AAAC Tree Wire Spacer Cable

  • Conductor 6201-81 aluminum alloy (AAAC)
  • Insulation Cross-linked polyethylene(XLPE)
  • Sheath High-density track-resistant Polyethylene(HDPE)
  • Package Export wooden drum & iron wooden drum or as customer require


Conatact us


Name


Email


Phone


Message


Congratulations. Your message has been sent successfully.
Error, please retry. Your message has not been sent.

This cable is a specialized covered conductor for primary and secondary overhead distribution. It's designed for situations where space is limited, such as in congested areas or corridors. The cable's covering provides protection against direct shorts and flashovers with other objects, although it is not a fully insulated cable. The term '2-Layer' refers to the distinct layers of insulation and sheath.


Key Specifications & Construction

  • Voltage: 15 kV phase-to-phase
  • Conductor: Concentrically stranded 6201-T81 aluminum alloy (AAAC). Other options like AAC or ACSR are also available.
  • Insulation: Cross-linked polyethylene (XLPE).
  • Sheath: A protective outer layer of high-density track-resistant polyethylene (HDPE).
  • Standards: The cable meets several standards, including ICEA S-121-733, ASTM B231, ASTM B399, and ASTM B232.

Technical Data

  • Normal Operating Temperature: C
  • Emergency Overload Temperature: C
  • Short Circuit Temperature: C
  • AC Testing Voltage: 27 kV for 5 minutes

Application

Tree wire is primarily used in overhead distribution systems to prevent outages caused by momentary contact with tree limbs or other objects. Its compact design and durable covering minimize the required space and hardware for installation, making it a reliable solution for:

  • Lines running through wooded areas 🌳
  • Congested urban alleyways
  • Rights-of-way where limited space is a concern
2-Layer 15kV AAAC Tree Wire Spacer Cable
Size
(kcmil)
Equivalent Stranding Conductor Covering Thickness Cable O.D. Rated Weight per
AAC (AWG or kcmil) Diameter (mils) (mils) Strength 1000 ft.
(mils) Inner Layer Outer Layer (lbs) (lbs)
48.69 4 7 250 75 75 550 1584 124
77.47 2 7 316 75 75 616 2520 165
123.3 1/0 7 398 75 75 698 4014 225
155.4 2/0 7 447 75 75 747 4851 265
195.7 3/0 7 502 75 75 802 6111 314
246.9 4/0 7 563 75 75 863 7704 376
312.8 266.8 19 642 75 75 942 9900 450
394.5 336.4 19 720 75 75 1020 11970 543
465.4 397.5 19 782 75 75 1082 14040 623
559.5 477 19 858 75 75 1158 16920 727
652.4 556.5 19 927 75 75 1227 19710 828
740.8 636 37 990 80 80 1310 21960 938
25kV SAC Cable
Nominal Size Min. No.
of Wires
Covering Thickness Cable Diameter Min. Breaking Load Weight
Conductor Shield Inner Layer Outer Layer
mm² No. mm mm mm  mm N kg/km
3-Layer 25kV AAC/XLPE/HDPE
25 6 0.70 3.18 3.18 20.1 3762 356
35 6 0.70 3.18 3.18 21.1 5177 404
50 6 0.70 3.18 3.18 22.2 7011 461
70 12 0.70 3.18 3.18 23.9 10354 555 
95 15 0.70 3.18 3.18 25.7 13727 664
120 15 0.70 3.18 3.18 26.9 17339 755
150 15 0.70 3.18 3.18 28.6 21033 864
185 30 0.70 3.18 3.18 30.2 26732 997
240 30 0.70 3.18 3.18 32.5 34679 1203
Need Help?